FREE IEC Electrical Calculations and Theory Questions and Answers

0%

What reading will the voltmeter display if its leads are connected to T3 and T4?

Correct! Wrong!

Explanation:
When the leads of the voltmeter are placed at T3 and T4, the meter will indicate 120 volts. This is because T3 and T4 represent the hot legs of a split-phase 240-volt system, and measuring between them gives the voltage across one phase, which is typically 120 volts in a residential electrical system.

How much is allowed for each branch circuit serving laundry receptacles when calculating residential service load?

Correct! Wrong!

Explanation:
When calculating residential service load, 1,500 volt-amperes are allowed for each branch circuit serving laundry receptacles. This allowance accounts for the typical load of laundry appliances such as washing machines and dryers, ensuring that the electrical system is adequately sized to handle the expected demand.

How much current is flowing in the neutral conductor if circuits 7 and 9, sharing a neutral in a multi-wire branch circuit, draw 13 amps and 16 amps, respectively?

Correct! Wrong!

Explanation:
In a multi-wire branch circuit, the neutral current is calculated by summing the unbalanced currents of the circuits sharing the neutral. In this case, circuit 7 is drawing 13 amps, and circuit 9 will draw 16 amps. Therefore, the unbalanced current is 3 amps (16 amps - 13 amps). So, 3 amps is flowing in the neutral.

How many feet should an extension ladder extend above the top of a building to ensure proper safety and be securely anchored?

Correct! Wrong!

Explanation:
An extension ladder should extend 3 feet above the top of the building and be secured. This extension provides stability and ensures safe access to and from the roof or elevated area.

What is the minimum quantity of receptacles needed in an unfinished basement?

Correct! Wrong!

Explanation:
The minimum number of receptacles required in an unfinished basement is 1. This receptacle is typically installed within 6 feet of the stairs, and additional receptacles are recommended at regular intervals along the walls to ensure adequate access to power throughout the space.

What should be minimized to reduce conductor insulation damage and arcing damage to electrical equipment during a ground fault or short circuit?

Correct! Wrong!

Explanation:
To minimize conductor insulation damage and arcing damage to electrical equipment during a ground fault or a short circuit, the time duration of the fault should be minimized. Shortening the duration reduces the amount of heat generated and the potential for damage, helping to protect both the conductors and the electrical equipment connected to them.

What term accurately describes a service lateral?

Correct! Wrong!

Explanation:
A service lateral typically refers to the underground feed that connects the utility service to a building's electrical distribution system. It's an underground conduit or cable that delivers electrical power from the utility's distribution system to the service entrance of a building.

How many kilowatt-hours (kWh) will the utility bill for if a 60-watt lamp operates continuously for 21 hours?

Correct! Wrong!

Explanation:
To calculate the kWh (kilowatt-hours) consumed by the lamp, multiply the wattage of the lamp by the hours it operates:
60 watts × 21 hours = 1260 watt-hours

Then, convert watt-hours to kilowatt-hours by dividing by 1000:
1260 watt-hours ÷ 1000 = 1.260 kWh

So, the utility will bill for 1.260 kWh.

What is the monthly expense for operating a 250-watt high-pressure sodium lamp? The electricity is priced at $0.15 per kWh, and the lamp will be in operation for 8 hours each day, with a billing month consisting of 30 days.

Correct! Wrong!

Explanation:
To calculate the monthly energy cost, first, determine the energy consumption per day:
Energy consumption per day = Power of lamp (in kW) × Hours of operation per day
Energy consumption per day = (250 W / 1000) kW × 8 hours = 2 kWh

Then, calculate the total energy consumption for the month:
Total energy consumption for the month = Energy consumption per day × Days in a billing month
Total energy consumption for the month = 2 kWh/day × 30 days = 60 kWh

Finally, determine the total cost:
Total cost = Total energy consumption × Cost per kWh
Total cost = 60 kWh × $0.15/kWh = $9.00

What voltage threshold, as per the Standard for Electrical Safety in the Workplace, necessitates de-energizing and locking out all electrical equipment before permitting work on or near it?

Correct! Wrong!

Explanation:
The Standard for Electrical Safety in the Workplace requires that all electrical equipment operating at over 50 volts to ground be de-energized and locked out before anyone is permitted to work on or near the equipment. This ensures the safety of workers by preventing accidental contact with live electrical components.

What is the smallest allowable AWG size for copper THHN/THWN conductors used in underground conductors for a 125-amp, 120/240-V, 3W residential service?

Correct! Wrong!

Explanation:
For a 125-amp, 120/240-V, 3W residential service, 2 AWG copper THHN/THWN conductors are the smallest permitted for the underground conductors. This gauge ensures that the conductors can safely carry the current without overheating or exceeding voltage drop limits over the distance of the underground run.