  1. Which scenario would result in the FDNY suspending or revoking an S-95 certificate? Failing to maintain the log book and repeatedly neglecting FDNY notifications
  2. Which component continuously monitors fire alarm field wiring for open circuits, ground faults, and short circuits? The panel's supervisory circuitry operating on each monitored circuit
  3. Which NFPA standard, rather than NFPA 72 itself, primarily governs where smoke detectors must be installed within HVAC air distribution ductwork? NFPA 90A
  4. Which of the following best describes the primary power source for a Fire Alarm Control Panel (FACP)? A dedicated branch circuit with a marked and locked circuit breaker.
  5. After activation, which type of heat detector must be replaced rather than reset? Fusible-link or fusible-alloy fixed-temperature detector
  6. The purpose of a 'waterflow retard' on a wet-pipe sprinkler system alarm check valve is to: Delay the alarm signal to reduce false activations from surges
  7. The NFPA 72 'record of completion' must be signed by: The contractor or installer responsible for the installation
  8. During a fire drill, the S-95 holder's role includes: Coordinating with building staff and documenting the drill in the log book
  9. Which consequence can a building owner face for repeatedly ignoring AHJ orders to repair a non-functional fire alarm system? Forced building closure, fines, and potential criminal liability
  10. An ionization smoke detector is generally more responsive than a photoelectric detector to: Fast, flaming fires with small, invisible combustion particles.
  11. In most US jurisdictions, which agency enforces fire alarm system code compliance in existing commercial buildings? Local fire marshal or fire prevention bureau
  12. Per NFPA 72, what is the minimum sound pressure level required for audible notification appliances in sleeping areas? 75 dB at the pillow
  13. The 'reset' function on an FACP is primarily used to: Return the system to normal standby after alarm or trouble conditions have been cleared
  14. According to NFPA 72, smoke detector sensitivity must first be tested within how long after initial installation? Within 1 year of installation
  15. Which of the following events would typically initiate a 'Trouble' signal at the FACP? A loss of primary AC power to the FACP.
  16. Visible notification appliances (strobes) are required in locations where: Ambient noise levels may prevent audible signals from being heard
  17. A projected beam smoke detector consists of which two primary components? Transmitter and receiver
  18. A fire alarm supervisor discovers a technician falsified inspection records. What is the supervisor's legal obligation? Correct the records and report the falsification
  19. What is the purpose of a fire alarm system inspection report? To summarize the findings of routine inspections and any corrective actions taken
  20. When a notification appliance circuit (NAC) develops an open-circuit fault, the fire alarm control unit will typically: Display a trouble condition indicating the circuit fault
  21. Which condition indicates that the OS&Y valve is properly maintained and functioning as intended? The stem is extended with the yoke in a vertical position.
  22. Under NFPA 72, sealed lead-acid (SLA) batteries used in fire alarm systems must be replaced at a maximum interval of: Every 5 years
  23. Which regulation requires that fire alarm systems in certain federally regulated facilities comply with ADA accessibility standards? The Americans with Disabilities Act (ADA)
  24. When does NFPA 72 require a new acceptance test to be performed on an existing fire alarm system? After any addition, modification, or deletion of system components
  25. A partially closed sprinkler system control valve would generate which type of FACP signal? Supervisory signal
  26. Voice evacuation systems use which type of notification appliance to deliver intelligible emergency instructions? Speakers
  27. A fire alarm control unit displays a 'common alarm' condition. This means: At least one initiating device in the system has activated an alarm condition
  28. A smoke detector in a corridor repeatedly goes into alarm during early morning hours with no visible smoke present. The MOST likely cause is: High humidity or condensation affecting the detector chamber
  29. A fire alarm system 'impairment' is defined as a condition in which: Part or all of the fire protection system is out of service
  30. A 'trouble' signal displayed on a fire alarm control panel indicates: A fault or abnormal condition within the fire alarm system itself