Fire Alarm System Operation Flashcards
21 cards from real S95 practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 20 Fire Alarm System Operation flashcards as text
During a fire alarm signal, the control unit begins a pre-signal delay before notifying occupants. What is the primary purpose of this delay?
Answer: To permit trained personnel to investigate and confirm the alarm before general evacuation
A pre-signal (or presignal) delay allows designated staff to investigate the alarm source before general notification, reducing unnecessary evacuations.
A smoke detector in a corridor repeatedly goes into alarm during early morning hours with no visible smoke present. The MOST likely cause is:
Answer: High humidity or condensation affecting the detector chamber
High humidity or condensation can cause ionization and photoelectric detectors to alarm nuisance-free by mimicking smoke particle density in the sensing chamber.
According to NFPA 72, a single station smoke alarm differs from a system smoke detector primarily because it:
Answer: Contains its own integral notification appliance and is self-contained
A single station alarm integrates the detector and notification appliance in one unit, operating independently without a central control panel.
A fire alarm control unit (FACU) is in the 'silenced' condition. Which of the following statements is TRUE?
Answer: Audible notification has been silenced but visual indicators and alarm condition remain active
Silencing only quiets audible appliances; the FACU remains in alarm condition with visual indicators active until the system is fully reset.
Which component in a fire alarm system is responsible for converting a detected condition into an electrical signal sent to the control unit?
Answer: Initiating device
Initiating devices such as smoke detectors, heat detectors, and manual pull stations sense a condition and send a signal to the FACU.
A fire alarm system supervisory signal is generated when:
Answer: A sprinkler system valve is found in a partially closed position
Supervisory signals indicate an off-normal condition in a fire protection system, such as a closed or partially closed sprinkler control valve.
In a fire alarm system, Class B wiring differs from Class A wiring primarily in that Class B:
Answer: Does not provide continuity of operation when a single open fault occurs
Class B circuits will lose communication to devices beyond a single open fault, whereas Class A circuits use a loop that maintains operation despite one open.
When a fire alarm control unit receives a ground fault indication, the supervisor should FIRST:
Answer: Notify the authority having jurisdiction (AHJ) and arrange for prompt repair
A ground fault is a trouble condition that must be reported to the AHJ and corrected promptly, as it can impair system reliability.
Rate-of-rise heat detectors respond to which fire condition?
Answer: A rapid increase in temperature over a short time period
Rate-of-rise detectors activate when temperature increases at a rate exceeding approximately 12–15°F per minute, regardless of the actual temperature reached.
A fire alarm system with a 'positive alarm sequence' (PAS) feature allows:
Answer: Trained personnel up to 3 minutes to investigate before general evacuation signals sound
Under NFPA 72, PAS gives trained staff up to 3 minutes (180 seconds) to acknowledge and investigate before general notification is initiated.
An addressable fire alarm system differs from a conventional system in that it:
Answer: Can identify the specific device in alarm or trouble by its unique address
Addressable systems assign each device a unique identifier, allowing the control panel to pinpoint exactly which device is reporting an alarm or fault.
Which of the following is the CORRECT action when a fire alarm system is taken out of service for maintenance exceeding four hours?
Answer: Provide a fire watch and notify the AHJ and supervising station
NFPA 72 and most fire codes require a fire watch when a fire alarm system is impaired, along with notification to the AHJ and supervising station.
What does a 'trouble' signal on a fire alarm control unit indicate?
Answer: A fault in the system wiring, power supply, or component that requires service
A trouble signal indicates the system has detected an abnormal condition such as a wiring fault, ground fault, or component failure that requires service.
In the context of fire alarm systems, what is the function of an 'End-of-Line' (EOL) resistor?
Answer: It allows the control panel to supervise the circuit for open or short faults
An EOL resistor placed at the end of a Class B circuit allows the FACU to continuously monitor the loop for opens or shorts by measuring circuit impedance.
In a fire alarm system, the term 'alarm verification' refers to a feature that:
Answer: Introduces a time delay to re-sample detector input before transmitting an alarm signal
Alarm verification temporarily clears the initiating device input and re-evaluates it to reduce nuisance alarms caused by transient conditions.
Which type of occupancy is MOST likely to require a voice evacuation system rather than audible tone-only notification?
Answer: High-rise buildings above 75 feet in height
High-rise buildings typically require voice/alarm communication systems (VACS) to provide specific evacuation instructions to occupants on each floor.
A photoelectric smoke detector operates on which principle?
Answer: Interruption or scattering of a light beam by smoke particles
Photoelectric detectors use a light source and sensor; smoke particles scatter light onto the sensor, triggering an alarm.
A supervisory signal from a sprinkler system pressure switch would MOST likely indicate:
Answer: Air or water pressure in the system has deviated from normal operating range
A pressure supervisory switch monitors system pressure and signals an off-normal condition when pressure falls outside acceptable limits, indicating a potential leak or tampering.
When performing a fire alarm system inspection, the supervisor notices a smoke detector has a painted-over grille. The CORRECT action is to:
Answer: Tag the detector as failed and replace it, since paint compromises sensing chamber entry
Paint over a detector grille blocks airflow into the sensing chamber, rendering the detector non-functional; it must be replaced.
A fire alarm control unit displays a 'common alarm' condition. This means:
Answer: At least one initiating device in the system has activated an alarm condition
A 'common alarm' LED or indicator on the FACU simply signals that one or more initiating devices are in an alarm state.