Supervisory and Trouble Signals Flashcards
7 cards from real S95 practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 7 Supervisory and Trouble Signals flashcards as text
When a fire alarm system is placed in 'test mode' by an authorized person, the monitoring station should be:
Answer: Notified by phone before testing begins
Before placing a fire alarm system in test mode, the central station or monitoring company must be notified by phone to prevent unnecessary emergency responses.
A 'ground fault' trouble on a Class A initiating device circuit is MOST likely caused by:
Answer: Insulation damage causing a conductor to contact a grounded surface
A ground fault occurs when damaged wire insulation allows a conductor to make contact with a grounded surface such as conduit or a metal enclosure.
What distinguishes a 'supervisory' signal from an 'alarm' signal in terms of required response urgency?
Answer: Alarm signals indicate emergency conditions while supervisory signals indicate off-normal conditions requiring investigation
Alarm signals indicate an emergency requiring immediate evacuation and fire department notification, while supervisory signals indicate off-normal conditions that need investigation but not immediate evacuation.
A dry-pipe valve that has tripped and allowed air to escape from the system would generate what type of signal?
Answer: Alarm signal from the associated flow switch
When a dry-pipe valve trips, water flows into the system piping and the flow switch activates, generating an alarm signal just like a wet-pipe system.
Which NFPA 72 signal category is associated with a 'low air pressure' condition on a dry-pipe or pre-action sprinkler system?
Answer: Supervisory
Low air pressure in a dry-pipe or pre-action system is a supervisory signal because it indicates the system's supervised condition is off-normal but has not yet operated.
A fire alarm system technician notices the FACP shows a trouble signal labeled 'NAC open.' What does this mean?
Answer: The notification appliance circuit has an open wiring fault
A NAC (Notification Appliance Circuit) open trouble indicates a break in the circuit wiring that would prevent notification appliances from sounding during an alarm.
Under NFPA 72, if a fire alarm system trouble condition cannot be corrected within 24 hours, the responsible party MUST:
Answer: Implement a fire watch until repairs are made
When a fire alarm trouble condition cannot be corrected promptly, NFPA 72 and most fire codes require implementing a fire watch to maintain occupant safety.
How this page was made: written with AI tools and published by Nathan Beja, founder of Practice Test Geeks, who is responsible for its content. Exam facts are checked against the official sources listed below. Not reviewed by a subject-matter expert. Editorial policy