← All S95 Flashcard Decks

Regulatory Codes and Requirements Flashcards

6 cards from real S95 practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 6 Regulatory Codes and Requirements flashcards as text
  1. According to the NYC Fire Code, when a required fire alarm system is out of service, who is the building owner required to designate to take required actions, such as implementing a fire watch?

    Answer: An Impairment Coordinator.

    NYC Fire Code Section 901.7.1 explicitly states that the building owner shall designate an 'Impairment Coordinator' to take the actions required when a fire alarm system is out of service. In the absence of a specific designee, the owner is considered the impairment coordinator.

  2. A fire alarm system at a protected premises uses a single communication path to transmit signals to the supervising station. What is the maximum interval at which this communication path must be supervised, according to NFPA 72?

    Answer: Every 60 minutes

    NFPA 72, Section 26.6, requires that a single communication path to a supervising station be supervised at intervals not exceeding 60 minutes. If multiple paths are used, the interval is extended to 6 hours.

  3. An S-95 holder is working in a building where the owner has decided to install a fire alarm system, even though it is not required by the NYC Building Code for that specific occupancy type. Which of the following is true regarding this non-required system?

    Answer: The system must still meet the design and installation requirements of the NYC Fire Code and Building Code.

    According to the NYC Fire Code (Section 901.4.2), any fire protection system installed, even if not required by code, must meet the applicable requirements of the Fire Code, rules, and construction codes as if it were a required system.

  4. During a planned fire alarm system test, what is a critical notification requirement that must be met before any testing begins, as per NFPA 72?

    Answer: Notify all persons and facilities receiving signals, as well as all building occupants.

    NFPA 72 Section 14.2.4.1 mandates that before proceeding with any testing, all persons and facilities that receive alarm, supervisory, or trouble signals (like the central station) and all building occupants must be notified to prevent unnecessary response and confusion.

  5. A new fire alarm system is being installed in a commercial office building in NYC. According to the NYC Building Code (BC 907), what must happen before the system can be installed?

    Answer: Design and installation documents must be submitted to and approved by the FDNY.

    Section BC 907 of the NYC Building Code specifies that documents for fire alarm systems, including design and installation plans, must be submitted for review and approval to the Fire Department before the system is installed.

  6. Which of the following is a specific regulatory requirement for the S-95 Certificate of Fitness itself?

    Answer: It is valid only at a specific location and for the specific person to whom it is issued.

    The regulations for the S-95 Certificate of Fitness clearly state that the certificate is site-specific and non-transferable. It is valid only for the person to whom it is issued and only at the specific work location listed on the certificate.