← All S95 Flashcard Decks

Inspection and Testing Procedures Flashcards

7 cards from real S95 practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 7 Inspection and Testing Procedures flashcards as text
  1. What is the maximum allowable response time from the initial alarm to notification appliance activation for a fire alarm system without voice evacuation?

    Answer: 30 seconds

    NFPA 72 requires notification appliances to activate within 10 seconds of alarm initiation for systems without voice evacuation, but the commonly tested maximum for signal processing is 10 seconds; however, the standard most often referenced for audible output response is 10 seconds from signal to sound.

  2. During an acceptance test, a technician discovers that a fire alarm control panel annunciator is not displaying the correct zone location for a triggered device. This is classified as a:

    Answer: Deficiency that must be corrected before the system is accepted

    Incorrect annunciation can delay emergency responders, so it is a deficiency that must be corrected before the system can be accepted and placed in service.

  3. A fire alarm system's secondary power source (batteries) must be tested under load to verify capacity. The test is performed by:

    Answer: Disconnecting primary power and monitoring system operation for 24 hours plus 5 minutes of alarm load

    Battery capacity is verified by disconnecting AC power and confirming the system remains operational for 24 hours standby plus 5 minutes in full alarm.

  4. Which of the following initiating device types requires a 'special listing' test method because aerosol smoke cannot reliably activate it?

    Answer: Air-sampling (aspirating) smoke detectors

    Air-sampling (aspirating) detectors require special testing methods because the dilution in the sampling pipe makes aerosol smoke tests unreliable.

  5. What is the required minimum frequency of testing for a fire alarm system in a high-rise building with a central supervising station connection?

    Answer: Annually for all devices

    NFPA 72 Table 14.4.5 requires annual inspection and testing of fire alarm system components in most occupancies including high-rise buildings.

  6. When a technician performs an end-to-end test of a digital alarm communicator transmitter (DACT), the test must confirm that a signal is received at:

    Answer: The supervising station within 90 seconds

    The DACT end-to-end test must confirm successful signal delivery to the supervising station, and NFPA 72 requires this within 90 seconds.

  7. Under NFPA 72, who is ultimately responsible for ensuring that fire alarm system inspections, testing, and maintenance are performed on schedule?

    Answer: The property owner or their designated representative

    NFPA 72 places the responsibility for scheduling and ensuring inspections, testing, and maintenance on the property owner or their designated representative.

How this page was made: written with AI tools and published by Nathan Beja, founder of Practice Test Geeks, who is responsible for its content. Exam facts are checked against the official sources listed below. Not reviewed by a subject-matter expert. Editorial policy

Sources & references

Exam facts on this page (fees, format, dates, passing scores) are checked against these official sources; the date is our last check. Editorial policy

  1. nyc.gov — Fees, renewal, score validity, eligibility, retake policy, score release, test dates, test delivery, exam format, passing score · verified Oct 2026