Mixed Deck — All Licensed Electrical Contractor Topics Flashcards
100 cards from real Licensed Electrical Contractor practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 20 Mixed Deck — All Licensed Electrical Contractor Topics flashcards as text
When calculating dryer load for a multifamily dwelling with 15 dryers, what demand factor applies per NEC Table 220.54?
Answer: 47%
For 15 dryers, NEC Table 220.54 specifies a demand factor of 47%.
What is the minimum required height for overhead service conductors crossing a commercial parking lot subject to truck traffic?
Answer: 18 feet
NEC 225.18 requires overhead conductors to maintain at least 18 feet of clearance over areas subject to truck traffic.
What is the minimum rating required for any branch circuit that supplies two or more outlets or receptacles per NEC 210.3?
Answer: 15 amperes
NEC 210.3 establishes that branch circuit ratings shall not be less than the maximum load to be served, with 15 amperes being the minimum standard rating.
Per NEC 334.80, what is the maximum ambient temperature rating for standard Type NM cable?
Answer: 90°C
NEC 334.80 states that Type NM cable is rated at 90°C but the ampacity must be based on the 60°C column per the conductor temperature limitation.
Which type of insurance is mandatory in most states for an electrical contracting business as soon as it hires its first employee?
Answer: Workers' Compensation Insurance
Workers' compensation insurance is legally required in most states for businesses with employees. It covers medical expenses, lost wages, and rehabilitation costs for employees who are injured or become ill on the job. While other insurance types are essential, workers' compensation is the specific coverage directly tied to the act of employing staff.
Under NEC 110.16, arc-flash hazard warning labels are required on electrical equipment likely to require examination, adjustment, servicing, or maintenance while energized in which occupancy types?
Answer: Other than dwelling units
NEC 110.16 requires arc-flash warning labels on switchboards, panelboards, and similar equipment in other than dwelling units.
For a dwelling unit with 240-volt electric range rated at 12 kW, what is the maximum demand load permitted per NEC Table 220.55 Column C?
Answer: 8 kW
NEC Table 220.55 Column C permits an 8 kW maximum demand for a single household range rated up to 12 kW.
A subcontractor's bond that guarantees the subcontractor will complete the work per the contract is called a:
Answer: Performance bond
A performance bond guarantees that the bonded contractor will complete the project according to the contract terms, protecting the project owner if the contractor defaults.
When a metal water pipe is used as a grounding electrode, it must be supplemented by an additional electrode unless the pipe meets which condition?
Answer: No supplemental electrode is ever required with metal water pipes
NEC 250.53(D)(2) always requires a supplemental electrode when using a metal underground water pipe as a grounding electrode.
When should you replace a circuit breaker?
Answer: When they fail to reset or show damage.
Circuit breakers are designed to trip to protect circuits from overloads or short circuits. While occasional tripping is normal under fault conditions, a breaker that repeatedly trips, fails to reset, or shows visible signs of damage (like scorch marks or a burning smell) indicates a serious internal fault. In such cases, the breaker has likely failed internally and must be replaced to ensure continued circuit protection and safety.
Which NEC article governs the installation of emergency power systems in commercial buildings?
Answer: Article 700
NEC Article 700 covers emergency systems that are legally required and classified as essential for safety to human life.
Per NEC 230.42, service entrance conductors must have sufficient ampacity to carry the current for the load as determined by which article?
Answer: Article 220
NEC 230.42(A) requires service entrance conductors to be sized per the load calculations in Article 220.
What is a primary requirement of a rapid shutdown system for a rooftop solar PV system, according to NEC Article 690.12, designed to enhance firefighter safety?
Answer: To reduce the voltage of controlled conductors OUTSIDE the array boundary to not more than 30 volts within 30 seconds of initiation.
The main purpose of PV rapid shutdown, as outlined in NEC 690.12, is to protect first responders. It requires that controlled conductors outside the array boundary (more than 1 ft from the array) be reduced to not more than 30 volts within 30 seconds of initiation. It also requires conductors inside the array boundary to be reduced to 80 volts within 30 seconds.
When applying the optional calculation method for a dwelling unit, what is the minimum load in volt-amperes applied to the first 10 kVA of all other loads?
Answer: 100%
Under NEC 220.82, the first 10 kVA of all other loads is calculated at 100%, with the remainder at 40%.
According to the NEC, what is the minimum burial depth for rigid metal conduit (RMC) installed under a residential driveway?
Answer: 6 inches
NEC Table 300.5 requires a minimum cover of 6 inches for RMC under areas subject to vehicular traffic.
What is the maximum number of 90-degree bends permitted in a single run of rigid metal conduit (RMC) between pull points?
Answer: Four 90-degree bends
NEC 358.26 and 344.26 limit conduit runs to the equivalent of four quarter bends (360 total degrees) between pull points, outlets, or junction boxes.
What is the NEC requirement for securing unused openings in electrical enclosures?
Answer: They must be effectively closed to provide protection equivalent to the enclosure wall
NEC 110.12(A) requires unused openings in electrical enclosures to be effectively closed to provide protection equivalent to the wall of the enclosure.
A commercial building experiences intermittent voltage sags. The utility feed tests normal. Where should the contractor investigate next?
Answer: Main distribution panel connections
Intermittent voltage sags with a normal utility feed most commonly originate from loose or corroded connections at the main distribution panel.
What is the maximum number of 180VA receptacle outlets permitted on a 20-ampere, 120-volt general-purpose branch circuit?
Answer: 13
A 20A circuit at 120V provides 2,400VA, and dividing by 180VA per outlet yields a maximum of 13 receptacle outlets.
When using a concrete-encased electrode (Ufer ground), what is the minimum length of bare copper conductor that must be encased in the concrete?
Answer: 20 feet
NEC 250.52(A)(3) requires at least 20 feet of bare copper conductor encased in concrete for a Ufer ground.
Written and edited by Nathan Beja, founder of Practice Test Geeks, with AI assistance. Exam facts are checked against the official sources linked below. Editorial policy
Sources & references
Exam facts on this page (fees, format, dates, passing scores) are checked against these official sources; the date is our last check. Editorial policy
- cslb.ca.gov — Eligibility, fees, renewal · verified Nov 2026
- www2.myfloridalicense.com — Exam format, passing score, retake policy, score release, time limit, test delivery, test dates · verified Nov 2026
- ncbeec.org — Test delivery, fees, exam format, passing score, retake policy, score release, test dates, time limit · verified Nov 2026