When applying the optional calculation method for a dwelling unit, what is the minimum load in volt-amperes applied to the first 10 kVA of all other loads?
Answer: 100%
Under NEC 220.82, the first 10 kVA of all other loads is calculated at 100%, with the remainder at 40%.
A 240V, single-phase service feeds a 10 kW electric range. Using the standard calculation method, what demand load from NEC Table 220.55 applies for one range?
Answer: 8 kW
NEC Table 220.55, Column C specifies an 8 kW demand for a single household range rated up to 12 kW.
What is the minimum size service required for a single-family dwelling under NEC 230.79?
Answer: 100 amperes
NEC 230.79(C) requires a minimum 100-ampere, 3-wire service for a single-family dwelling.
When calculating feeder neutral load for a residential service, how is the unbalanced load between lines reduced per NEC 220.61?
Answer: The portion of neutral load above 200A may be reduced by 70%
NEC 220.61(B)(1) permits the neutral load above 200A to be multiplied by 70% for further reduction.
A commercial occupancy has 50,000 VA of receptacle load. What demand factor applies to the receptacle load above 10,000 VA per NEC Table 220.44?
Answer: 50%
NEC Table 220.44 allows the receptacle load exceeding 10,000 VA to be calculated at 50% demand.
Which NEC article governs services, including the number of service disconnects permitted?
Answer: NEC Article 230
NEC Article 230 covers services, including the rule that no more than six disconnecting means are permitted.
When sizing a service for a building with multiple HVAC units, how are the hermetic refrigerant motor-compressor loads treated per NEC 440.6?
Answer: At the rated-load current or branch-circuit selection current, whichever is greater
NEC 440.6 requires using the rated-load current or branch-circuit selection current (whichever is larger) as the load for each hermetic compressor.
Written and edited by Nathan Beja, founder of Practice Test Geeks, with AI assistance. Exam facts are checked against the official sources linked below. Editorial policy
Sources & references
Exam facts on this page (fees, format, dates, passing scores) are checked against these official sources; the date is our last check. Editorial policy
- cslb.ca.gov — Eligibility, fees, renewal · verified Nov 2026
- www2.myfloridalicense.com — Exam format, passing score, retake policy, score release, time limit, test delivery, test dates · verified Nov 2026
- ncbeec.org — Test delivery, fees, exam format, passing score, retake policy, score release, test dates, time limit · verified Nov 2026