  1. In a patient care area of a healthcare facility, what is the maximum impedance permitted for the equipment grounding path from a receptacle to the grounding bus of the panel?

    Answer: 0.1 ohm

    NEC 517.13 and testing standards require the grounding path impedance in patient care vicinities not to exceed 0.1 ohm to protect patients from electric shock.

  2. What type of seal is required where a conduit passes from a Class I, Division 2 location into an unclassified area?

    Answer: A conduit seal fitting within 18 inches of the boundary

    NEC 501.15(B)(2) requires a conduit seal within 18 inches of the boundary where conduit leaves a Class I, Division 2 area and enters an unclassified space.

  3. Per NEC Article 625, what is the minimum branch circuit rating required for a Level 2 electric vehicle charging station rated at 32 amps continuous?

    Answer: 40 amperes

    Continuous loads must be sized at 125% of the load current, so 32A x 1.25 = 40A minimum branch circuit rating per NEC 625.41.

  4. Which of the following areas is classified as a Class I, Zone 0 hazardous location?

    Answer: The interior of a closed process vessel containing flammable liquid under normal conditions

    Zone 0 is defined as an area where ignitable concentrations of flammable gases or vapors exist continuously or for long periods, such as inside a closed process vessel.

  5. When installing a hot tub outdoors, what is the minimum distance that a 15- or 20-ampere receptacle must be located from the inside wall of the hot tub?

    Answer: 6 feet

    NEC 680.43(A) requires 15- and 20-ampere receptacles to be located at least 6 feet from the inside walls of a hot tub.

  6. In a commercial garage where flammable fuel is dispensed, up to what height above the floor is the area typically classified as a Class I, Division 2 location?

    Answer: 18 inches

    NEC 511.3(B) classifies the area up to 18 inches above the floor of a commercial repair garage as Class I, Division 2 due to heavier-than-air flammable vapors.

Written and edited by , founder of Practice Test Geeks, with AI assistance. Exam facts are checked against the official sources linked below. Editorial policy

Sources & references

Exam facts on this page (fees, format, dates, passing scores) are checked against these official sources; the date is our last check. Editorial policy

  1. cslb.ca.gov — Eligibility, fees, renewal · verified Nov 2026
  2. www2.myfloridalicense.com — Exam format, passing score, retake policy, score release, time limit, test delivery, test dates · verified Nov 2026
  3. ncbeec.org — Test delivery, fees, exam format, passing score, retake policy, score release, test dates, time limit · verified Nov 2026
Licensed Electrical Contractor Special Occupancies and Equipment Questions and Answers Flashcards — Licensed Electrical Contractor Study Cards with Answers