← All Licensed Electrical Contractor Flashcard Decks

Licensed Electrical Contractor Motors and Motor Controls Questions and Answers Flashcards

6 cards from real Licensed Electrical Contractor practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 6 Licensed Electrical Contractor Motors and Motor Controls Questions and Answers flashcards as text
  1. What happens to a three-phase induction motor if one phase of the supply is lost while the motor is running?

    Answer: The motor continues to run at reduced power on single phase

    A running three-phase motor will continue to operate on single phase but at reduced power and with increased current draw, which can cause overheating if not protected.

  2. Which NEC article specifically covers the installation requirements for motor circuits and controllers?

    Answer: Article 430

    NEC Article 430 covers motors, motor circuits, and controllers, including installation, protection, and control requirements.

  3. What is the purpose of a holding contact (seal-in contact) in a motor starter circuit?

    Answer: To maintain the contactor coil circuit after the start button is released

    The holding contact bypasses the momentary start pushbutton to keep the contactor energized after the operator releases the start button.

  4. According to NEC 430.32, what is the maximum continuous motor overload protection setting for a motor with a marked service factor of 1.15 or greater?

    Answer: 125% of nameplate FLA

    NEC 430.32(A)(1) allows overload protection up to 125% of the nameplate full-load current for motors with a service factor of 1.15 or greater.

  5. In a wye-delta motor starter, what is the primary advantage of starting the motor in the wye configuration?

    Answer: Starting current is reduced to approximately one-third of delta starting current

    In wye configuration, the voltage across each winding is reduced by a factor of 1/sqrt(3), resulting in approximately one-third the starting current compared to delta.

  6. What is the required grounding method for a motor frame per NEC 250.134?

    Answer: An equipment grounding conductor run with the circuit conductors

    NEC 250.134 requires equipment grounding conductors to be run with the circuit conductors to provide an effective ground-fault current path back to the source.

Written and edited by , founder of Practice Test Geeks, with AI assistance. Exam facts are checked against the official sources linked below. Editorial policy

Sources & references

Exam facts on this page (fees, format, dates, passing scores) are checked against these official sources; the date is our last check. Editorial policy

  1. cslb.ca.gov — Eligibility, fees, renewal · verified Nov 2026
  2. www2.myfloridalicense.com — Exam format, passing score, retake policy, score release, time limit, test delivery, test dates · verified Nov 2026
  3. ncbeec.org — Test delivery, fees, exam format, passing score, retake policy, score release, test dates, time limit · verified Nov 2026