Licensed Electrical Contractor Motors and Motor Controls Questions and Answers Flashcards
6 cards from real Licensed Electrical Contractor practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 6 Licensed Electrical Contractor Motors and Motor Controls Questions and Answers flashcards as text
What is the primary purpose of a reduced-voltage starter for an AC induction motor?
Answer: To limit inrush current during startup
Reduced-voltage starters limit the high inrush current that occurs when a motor is started across the line, protecting both the motor and the electrical system.
Per the NEC, what is the maximum allowable setting for a motor branch-circuit short-circuit and ground-fault protective device using an inverse-time circuit breaker for a standard AC motor?
Answer: 250% of the motor full-load current
NEC 430.52 permits inverse-time circuit breakers to be sized up to 250% of the motor full-load current for standard AC motors.
Which type of motor control method uses a Variable Frequency Drive (VFD) to adjust motor speed?
Answer: Frequency control
A VFD adjusts the frequency of the AC power supplied to the motor, which directly controls the synchronous speed of the motor.
What is the function of an overload relay in a motor control circuit?
Answer: To protect the motor from sustained overcurrent conditions
Overload relays are designed to protect motors from damage caused by sustained overcurrent conditions that exceed the motor's rated capacity.
When installing a motor disconnecting means, the NEC requires it to be located where?
Answer: Within sight of the motor and its controller
NEC 430.102(B) requires the disconnecting means to be in sight from the motor location and the driven machinery location for safety during maintenance.
A three-phase motor has a nameplate FLA of 40 amps. What is the minimum ampacity required for the branch-circuit conductors per NEC 430.22?
Answer: 50 amps
NEC 430.22 requires branch-circuit conductors to have an ampacity of not less than 125% of the motor full-load current, so 40 x 1.25 = 50 amps.
Written and edited by Nathan Beja, founder of Practice Test Geeks, with AI assistance. Exam facts are checked against the official sources linked below. Editorial policy
Sources & references
Exam facts on this page (fees, format, dates, passing scores) are checked against these official sources; the date is our last check. Editorial policy
- cslb.ca.gov — Eligibility, fees, renewal · verified Nov 2026
- www2.myfloridalicense.com — Exam format, passing score, retake policy, score release, time limit, test delivery, test dates · verified Nov 2026
- ncbeec.org — Test delivery, fees, exam format, passing score, retake policy, score release, test dates, time limit · verified Nov 2026