  1. When performing a standard load calculation for a single-family dwelling per NEC Article 220, what is the general lighting load allowance per square foot?

    Answer: 3 VA per square foot

    The NEC specifies a general lighting load of 3 VA per square foot for dwelling units.

  2. What is the demand factor applied to the first 10 kVA of general lighting and receptacle loads in a dwelling unit calculation?

    Answer: 100%

    The first 10 kVA of general lighting and receptacle loads is calculated at 100% demand factor per NEC Table 220.42.

  3. A 200-amp residential service uses a split-bus panel. How many main disconnect throws are permitted maximum?

    Answer: 6

    NEC 230.71 permits a maximum of six switches or circuit breakers to serve as the service disconnecting means.

  4. When calculating dryer load for a multifamily dwelling with 15 dryers, what demand factor applies per NEC Table 220.54?

    Answer: 47%

    For 15 dryers, NEC Table 220.54 specifies a demand factor of 47%.

  5. What minimum service size does the NEC require for a single-family dwelling?

    Answer: 100 amperes

    NEC 230.79(C) requires a minimum 100-ampere service for single-family dwellings.

  6. In a commercial load calculation, what demand factor is applied to the first 12.5 kVA of general lighting for an office building?

    Answer: 100%

    NEC Table 220.42 requires the first 12.5 kVA of general lighting load to be calculated at 100% for commercial occupancies.