Per NEC Article 680, what is the minimum burial depth for a direct-buried cable supplying a pool pump motor when not under a building or concrete?
Answer: 18 inches
NEC 680.10 and Table 300.5 require a minimum cover of 18 inches for direct-buried UF cable supplying pool equipment when not under a building or concrete.
In a Class II, Division 1 hazardous location containing combustible dust, which of the following enclosure types is required for electrical equipment?
Answer: Dust-ignitionproof enclosure
NEC Article 502 requires dust-ignitionproof enclosures in Class II, Division 1 locations to prevent ignition of combustible dust accumulations.
What is the required working space depth in front of electrical equipment rated 277 volts to ground with exposed live parts on one side and grounded parts on the other per NEC Table 110.26(A)(1)?
Answer: 3.5 feet
Per NEC Table 110.26(A)(1), Condition 2 at 151-600 volts requires a minimum working space depth of 3.5 feet.
Per NEC Article 511, above what height in a commercial repair garage are Class I, Division 2 requirements no longer applicable?
Answer: 18 inches above floor
NEC 511.3(A) classifies the area up to 18 inches above the floor as Class I, Division 2 in commercial garages where lighter-than-air gases are not present.
What bonding requirement does NEC Article 680 impose on metal parts of a pool structure, including reinforcing steel?
Answer: All metal parts must be bonded together with a minimum 8 AWG copper conductor
NEC 680.26 requires equipotential bonding of all metal parts associated with the pool structure using a minimum 8 AWG solid copper conductor.
In an assembly occupancy with more than 100 persons, what does NEC Article 518 require regarding the wiring methods used?
Answer: Wiring must be installed in metal raceways, nonmetallic raceways in concrete, Type MC or AC cable
NEC 518.4(A) requires wiring in places of assembly for 100+ persons to use metal raceways, nonmetallic raceways encased in concrete, or Type MC or AC cable.
Written and edited by Nathan Beja, founder of Practice Test Geeks, with AI assistance. Exam facts are checked against the official sources linked below. Editorial policy
Sources & references
Exam facts on this page (fees, format, dates, passing scores) are checked against these official sources; the date is our last check. Editorial policy
- cslb.ca.gov — Eligibility, fees, renewal · verified Nov 2026
- www2.myfloridalicense.com — Exam format, passing score, retake policy, score release, time limit, test delivery, test dates · verified Nov 2026
- ncbeec.org — Test delivery, fees, exam format, passing score, retake policy, score release, test dates, time limit · verified Nov 2026