FDNY Fire Life Safety Director (F-85/F-89) β Questions and Answers
Question 1: When must a fire pump be tested as part of a building's fire suppression maintenance program?
- Once every 5 years only
- Weekly for flow testing and annually for full performance testing (Correct answer)
- Only after any fire event
- Monthly for full flow and quarterly for churn testing
Correct answer: Weekly for flow testing and annually for full performance testing
NFPA 25 requires fire pumps to be run weekly (churn/no-flow test) and subjected to a full annual flow test to verify rated performance.
Question 2: A suspected anthrax letter is opened in a tenant's office on the 22nd floor. What is the IMMEDIATE first action?
- Evacuate the entire building through the stairwells
- Activate the fire suppression system to decontaminate the area
- Isolate the room, minimize movement of exposed persons, and call 911 and NYPD (Correct answer)
- Place the letter in a plastic bag and bring it to the Fire Control Room
Correct answer: Isolate the room, minimize movement of exposed persons, and call 911 and NYPD
Isolating the affected area and restricting movement of exposed individuals limits potential spread, while 911 and NYPD/HAZMAT must be notified for proper decontamination response.
Question 3: A new tenant finishes a space and installs ceiling tiles that are not listed or rated. Why does this violate fire code?
- Ceiling tiles in fire-rated assemblies must be tested and listed to maintain the assembly's fire resistance rating (Correct answer)
- Only tiles in exit corridors require a fire rating in commercial buildings
- Ceiling tiles must be UL listed only when installed above a certain height
- Unrated ceiling tiles are only prohibited in sprinklered buildings
Correct answer: Ceiling tiles in fire-rated assemblies must be tested and listed to maintain the assembly's fire resistance rating
When a ceiling is part of a fire-rated floor/ceiling assembly, all components including tiles must be listed and part of the tested assembly to preserve the rated protection.
Question 4: How often must a FLSD conduct fire drills in a high-rise office building under typical NYC Fire Code requirements?
- Twice per year (Correct answer)
- Once per quarter
- Once per year
- Once every two years
Correct answer: Twice per year
NYC Fire Code requires high-rise office buildings to conduct fire drills at least twice per year, typically one announced and one unannounced.
Question 5: The FLSD conducts quarterly training updates with floor wardens. The primary purpose of quarterly (versus annual) updates is to:
- Maintain warden proficiency, address personnel changes, and refresh procedures before they are forgotten (Correct answer)
- Comply with the building owner's insurance requirements
- Provide wardens with quarterly performance reviews
- Satisfy FDNY quarterly reporting requirements
Correct answer: Maintain warden proficiency, address personnel changes, and refresh procedures before they are forgotten
Quarterly updates maintain warden proficiency (skills degrade without practice), address turnover (new wardens need training), and refresh procedures before annual drills.
Question 6: During a fire, a floor warden discovers that the stairwell door on their floor is locked and cannot be opened. The floor warden should:
- Immediately contact the FLSD, direct occupants to the alternate stairwell, and have someone check for a key (Correct answer)
- Use an emergency break-glass to override the door lock
- Kick the door open to allow occupant passage
- Continue the evacuation through the locked door area
Correct answer: Immediately contact the FLSD, direct occupants to the alternate stairwell, and have someone check for a key
A locked stairwell door during fire evacuation is a critical emergency. The floor warden contacts the FLSD immediately, redirects occupants to an alternate stairwell, and attempts to locate a key.
Question 7: During a fire, smoke begins to infiltrate the floor where occupants are sheltering in place. The FLSD should advise these occupants to:
- Open windows to vent the smoke out of the space
- Use a stairwell immediately regardless of smoke levels there
- Move to an interior room, seal smoke entry points, and call 911 to update their location (Correct answer)
- Remain calm and wait β smoke will dissipate on its own
Correct answer: Move to an interior room, seal smoke entry points, and call 911 to update their location
When smoke infiltrates a shelter-in-place area, occupants should move deeper into the building interior, seal entry points, and update 911 with their exact location for rescue priority.
Question 8: During a fire emergency, a floor warden reports that heavy smoke is visible in Stairwell B on the 20th floor. The FLSD should:
- Open Stairwell B doors at multiple floors to ventilate the smoke
- Direct all occupants on floors 18-22 to use Stairwell B as the alternate route
- Instruct the floor warden to investigate the smoke source in Stairwell B
- Immediately direct all occupants away from Stairwell B and to use alternate stairwells; inform FDNY (Correct answer)
Correct answer: Immediately direct all occupants away from Stairwell B and to use alternate stairwells; inform FDNY
Smoke in a stairwell renders it unsafe for evacuation. The FLSD must immediately redirect all occupants to alternate stairwells and inform FDNY of the compromised stairwell.
Question 9: A medical emergency occurs on the 18th floor of a high-rise. The FLSD should use Phase I elevator recall to:
- Send all elevators to the 18th floor
- Send one elevator directly to the roof for helicopter access
- Lock all elevators in place to prevent use by the public
- Return all elevators to the ground floor lobby under FDNY control (Correct answer)
Correct answer: Return all elevators to the ground floor lobby under FDNY control
Phase I recall returns all elevators to the ground floor lobby, where FDNY takes control to respond to the emergency floor.
Question 10: In a NYC high-rise, the preferred method for determining the location of a fire when the alarm activates is:
- Asking building occupants which floor smells like smoke
- Manually searching each floor from top to bottom
- Waiting for visible smoke to determine which floor has the fire
- Reading the fire alarm control panel at the fire command station to identify the activated device (Correct answer)
Correct answer: Reading the fire alarm control panel at the fire command station to identify the activated device
The fire alarm control panel at the fire command station identifies exactly which detector or pull station activated and on which floor, providing immediate location information.
Question 11: What does it mean when a high-rise fire alarm activates with a 'temporal-3' audible pattern?
- Three short pulses followed by a pause β the standard fire alarm evacuation signal (Correct answer)
- A medical emergency has been detected on the floor
- The alarm is in test mode and occupants should disregard it
- The alarm is a supervisory signal requiring investigation only
Correct answer: Three short pulses followed by a pause β the standard fire alarm evacuation signal
The temporal-3 pattern (three short pulses repeated) is the standard ANSI/NFPA fire alarm evacuation signal β when occupants hear this pattern, they should treat it as a real fire emergency.
Question 12: During a fire emergency, a floor warden reports that a mobility-impaired occupant refuses to use the area of refuge and insists on using the elevator. What should the Fire Life Safety Director do?
- Allow the occupant to use the elevator since it is their personal choice
- Have the floor warden physically carry the occupant down the stairwell
- Direct the occupant to the area of refuge and notify firefighters of their location (Correct answer)
- Delay evacuation for that floor until the situation is resolved
Correct answer: Direct the occupant to the area of refuge and notify firefighters of their location
Elevators must not be used during fires; the FLSD should direct the occupant to the designated area of refuge and ensure responding firefighters are informed of the location.
Question 13: The FLSD is conducting annual recertification training for floor wardens. Which scenario-based exercise would BEST assess their readiness?
- A lecture reviewing the fire safety plan document
- A tabletop exercise simulating a partial-floor fire with missing wardens and communication challenges (Correct answer)
- A written multiple-choice test on fire code terminology
- A tour of the building's mechanical room
Correct answer: A tabletop exercise simulating a partial-floor fire with missing wardens and communication challenges
Tabletop scenario exercises that simulate realistic complicationsβlike absent wardens and communication failuresβare the most effective readiness assessments for floor wardens.
Question 14: A floor warden reports that half the occupants on their floor don't know who the floor warden is. The FLSD should:
- Remove the floor warden for failing to introduce themselves to all occupants
- Post warden identification in prominent locations and incorporate warden introduction into new employee orientation (Correct answer)
- Provide each occupant with the warden's personal phone number
- Assign two floor wardens to that floor until all occupants know who they are
Correct answer: Post warden identification in prominent locations and incorporate warden introduction into new employee orientation
Visibility of floor wardens can be improved by posting identification in common areas and ensuring new employee orientation includes a floor warden introduction β systematic solutions work better than individual effort.
Question 15: An occupant reports that they smell natural gas on the 8th floor. The FLSD should instruct all persons on the 8th floor to:
- Go to the roof where the gas concentration will be lower
- Evacuate the floor immediately without using light switches or any electrical equipment (Correct answer)
- Search the floor systematically to locate the gas source
- Open all windows and turn on HVAC to maximum for ventilation
Correct answer: Evacuate the floor immediately without using light switches or any electrical equipment
Upon smelling gas, all persons must evacuate the floor immediately without activating any electrical equipment (including light switches) which could spark and ignite the gas.
Question 16: How often should the FLSD provide training to fire wardens or emergency team members?
- Every six months.
- Quarterly.
- Monthly.
- Annually. (Correct answer)
Correct answer: Annually.
Fire Life Safety Directors (FLSDs) should provide training to fire wardens or emergency team members at least annually. This regular training ensures that wardens remain proficient in their duties, are updated on any changes to emergency plans or building systems, and can effectively guide occupants during an emergency. Ongoing education is crucial for maintaining a competent and ready emergency response team.
Question 17: A pre-action sprinkler system requires which condition before water is discharged?
- Only smoke detector activation
- A detection event AND sprinkler head activation (Correct answer)
- Heat alone activates sprinkler heads
- Manual override by the fire warden
Correct answer: A detection event AND sprinkler head activation
Pre-action systems require both a detection event (from a smoke or heat detector) and individual sprinkler head activation, providing two steps of confirmation before water flows.
Question 18: A sprinkler head discharges in an unoccupied storage room on a weekend with no fire detected. What should the on-duty FLSD do first?
- Shut off the main water supply to the entire building immediately
- Wait until Monday to report the incident to avoid unnecessary alarm
- Reset the fire alarm panel and resume normal operations
- Investigate the discharge location, notify 9-1-1, and contact building management (Correct answer)
Correct answer: Investigate the discharge location, notify 9-1-1, and contact building management
An unexpected sprinkler discharge requires investigation for a potential hidden fire, immediate notification of 9-1-1, and escalation to building management.
Question 19: The FLSD must ensure that floor warden training materials are available in:
- Spanish and Chinese only, per NYC requirements
- English only, as required by FDNY regulations
- All languages spoken by building occupants where practicable (Correct answer)
- PDF format stored on the building intranet only
Correct answer: All languages spoken by building occupants where practicable
Fire safety information should be made available in the languages spoken by building occupants to ensure all occupants understand emergency procedures.
Question 20: What information must be posted at the fire command station in a high-rise building?
- Tenant contact information and lease agreements
- Elevator service and inspection records
- Energy usage data and utility vendor contacts
- Building floor plans, fire alarm zone map, and emergency procedures (Correct answer)
Correct answer: Building floor plans, fire alarm zone map, and emergency procedures
The fire command station must display floor plans, alarm zone maps, and emergency procedures to enable rapid coordination during any incident.
Question 21: Under New York City fire code, how often must a high-rise office building conduct fire evacuation drills?
- Only when directed by the fire department
- Once every five years
- Monthly
- Twice per year, with at least one occurring during business hours (Correct answer)
Correct answer: Twice per year, with at least one occurring during business hours
NYC Fire Code requires high-rise office buildings to conduct fire drills at least twice per year, with at least one drill held during normal business hours.
Question 22: Which type of extinguisher is PROHIBITED from use on a Class K cooking fire involving burning grease?
- Water-mist extinguisher
- Class ABC dry chemical extinguisher (Correct answer)
- Carbon dioxide extinguisher
- Wet chemical extinguisher
Correct answer: Class ABC dry chemical extinguisher
Class ABC dry chemical extinguishers are prohibited on Class K fires because they can cause violent splatter of burning grease and do not effectively cool the fuel.
Question 23: The FLSD communicates the 'all clear' to occupants after FDNY authorization. The announcement should include:
- That the building is safe for re-entry, which floors may be affected or restricted, and any special instructions (Correct answer)
- An apology for the disruption caused by the emergency
- A detailed explanation of the cause of the emergency
- Only 'all clear β you may return' without additional details
Correct answer: That the building is safe for re-entry, which floors may be affected or restricted, and any special instructions
All-clear announcements must tell occupants the building is safe, identify any areas still restricted, and give specific re-entry instructions β not just a general 'all clear.'
Question 24: When should a floor warden use their floor warden kit's emergency flashlight?
- During monthly equipment checks to verify battery function
- Only when specifically directed by the FLSD via intercom
- During all fire drills to simulate night-time conditions
- During actual emergencies when power failure or smoke reduces visibility in the stairwell (Correct answer)
Correct answer: During actual emergencies when power failure or smoke reduces visibility in the stairwell
Flashlights in floor warden kits are for actual emergencies when visibility is reduced by power failure or smoke β they should be checked monthly but used when needed during real emergencies.
Question 25: Which training method is MOST effective for teaching building occupants the proper use of a fire extinguisher?
- Distributing written manuals
- Posting instructional signs near extinguishers
- Conducting hands-on live fire or simulation exercises (Correct answer)
- Showing an online video during orientation
Correct answer: Conducting hands-on live fire or simulation exercises
Hands-on practical exercises with actual or simulated fire scenarios produce the highest retention and competency for extinguisher use.
Question 26: What is the FLSD required to document after every fire drill?
- Total cost of the drill to submit for insurance reimbursement
- Only the names of occupants who did not participate
- Date, time, building areas involved, number of participants, deficiencies noted, and corrective actions (Correct answer)
- A list of fire extinguishers inspected during the drill
Correct answer: Date, time, building areas involved, number of participants, deficiencies noted, and corrective actions
Drill records must capture comprehensive data including deficiencies and corrective actions to satisfy regulatory requirements and improve future performance.
Question 27: What action should the FLSD take when a sprinkler head activates in a mechanical room?
- Reset the fire alarm panel immediately to silence the alarm
- Shut off the main water supply to prevent water damage
- Evacuate only the mechanical room occupants
- Investigate the area, confirm the activation, call 911, and implement the emergency plan (Correct answer)
Correct answer: Investigate the area, confirm the activation, call 911, and implement the emergency plan
Any sprinkler activation must be treated as a real fire emergency: confirm the situation, call 911, and execute the fire safety plan.
Question 28: What is the primary purpose of a building's Emergency Action Plan (EAP) as it relates to FLSD duties?
- To train new staff on building maintenance procedures
- To provide a written guide for coordinated emergency response and evacuation procedures (Correct answer)
- To document past fire incidents for legal protection
- To satisfy insurance requirements
Correct answer: To provide a written guide for coordinated emergency response and evacuation procedures
The EAP serves as the authoritative written guide ensuring all staff and occupants respond in a coordinated, pre-planned manner during emergencies.
Question 29: During a medical emergency, a floor warden reports that an occupant with a mobility disability cannot use the stairs. The FLSD should:
- Activate Phase II elevator service for the disabled occupant
- Instruct the occupant to wait in their office until help arrives
- Carry the occupant down the stairs personally
- Direct the occupant to the nearest area of refuge and notify FDNY of their location (Correct answer)
Correct answer: Direct the occupant to the nearest area of refuge and notify FDNY of their location
Occupants with mobility disabilities should be directed to areas of refuge, and FDNY must be notified of their exact location for rescue assistance.
Question 30: Which class of fire extinguisher is required for electrical equipment fires?
- Class B β for flammable liquids and gases
- Class A β for ordinary combustibles
- Class C β for energized electrical equipment (Correct answer)
- Class D β for combustible metals
Correct answer: Class C β for energized electrical equipment
Class C extinguishers use non-conductive agents (CO2, dry chemical, or clean agent) that are safe to use on energized electrical equipment without the risk of electrical shock.
Question 31: Which of the following should be included in a post-drill report submitted after a fire drill in a high-rise building?
- Names of all occupants who evacuated
- FDNY response time and unit numbers
- Time of drill, floors involved, deficiencies noted, and corrective actions taken (Correct answer)
- Insurance carrier notification and claim number
Correct answer: Time of drill, floors involved, deficiencies noted, and corrective actions taken
Post-drill reports must document the date and time, floors involved, any deficiencies observed, and corrective actions planned or taken.
Question 32: When a mobility-impaired occupant is waiting in an Area of Rescue Assistance during a fire evacuation, the FLSD must:
- Lock the stairwell door to protect the occupant until the all-clear is given
- Instruct the occupant to attempt stairwell descent independently using the handrail
- Evacuate the occupant via elevator to the ground floor immediately
- Inform arriving FDNY units of the occupant's exact location and condition (Correct answer)
Correct answer: Inform arriving FDNY units of the occupant's exact location and condition
The FLSD's critical duty is to relay the precise location and any relevant medical information about occupants in Areas of Rescue Assistance directly to arriving FDNY units, so firefighters can prioritize and execute assisted evacuation. Elevators are not used for evacuation, and occupants should not be forced into independent stairwell descent.
Question 33: The FLSD's emergency contact list should be updated:
- Only when FDNY requests a current copy
- Annually during the fire safety plan review
- Whenever there is a change in key personnel, tenants, or emergency contacts (Correct answer)
- After each fire drill regardless of whether changes occurred
Correct answer: Whenever there is a change in key personnel, tenants, or emergency contacts
The emergency contact list must be updated whenever any changes occur in key personnel, tenant contacts, or utility/service provider contacts β not just on a fixed schedule.
Question 34: During FDNY firefighting operations, the FLSD is asked to operate Phase II in a specific elevator. This means the FLSD should:
- Enter the elevator and operate it using the Phase II key switch inside the car as directed by FDNY (Correct answer)
- Use the fire command station to activate Phase II controls for the entire building
- Insert the Phase II key in the elevator machine room to control all cars remotely
- Release all elevators from Phase I and return them to normal service
Correct answer: Enter the elevator and operate it using the Phase II key switch inside the car as directed by FDNY
Phase II operation is performed by a person inside the elevator car using the car's Phase II key switch β giving manual control of that individual elevator.
Question 35: An active shooter is confirmed inside the building. Which response framework should the FLSD guide occupants to follow?
- CERT triage protocol
- RUN, HIDE, FIGHT (Correct answer)
- PASS β Pull, Aim, Squeeze, Sweep
- RACE β Remove, Alarm, Confine, Extinguish
Correct answer: RUN, HIDE, FIGHT
The Run, Hide, Fight protocol is the nationally recognized framework for active-shooter situations taught by FEMA and law enforcement.
Question 36: The concept of 'defend in place' in high-rise fire response means:
- The building's automatic suppression systems defend occupants without requiring evacuation
- Non-fire floors shelter in place rather than evacuating, relying on fire-rated construction for protection (Correct answer)
- Occupants are trained to fight fires on their floor before evacuating
- FDNY defends the building from outside rather than entering
Correct answer: Non-fire floors shelter in place rather than evacuating, relying on fire-rated construction for protection
Defend in place means that high-rise buildings are designed with compartmentalization so occupants on non-fire floors are protected by fire-rated construction and can shelter safely while fire is suppressed.
Question 37: A significant earthquake occurs while the building is occupied. The FLSD's first priority after shaking stops is to:
- Immediately evacuate all occupants via stairwells
- Activate the fire alarm to alert all occupants
- Contact the building owner for authorization to evacuate
- Conduct a rapid building assessment for structural damage before deciding whether to evacuate (Correct answer)
Correct answer: Conduct a rapid building assessment for structural damage before deciding whether to evacuate
After an earthquake, the FLSD must first assess for structural damage, fire, gas leaks, and utility disruptions before deciding whether immediate evacuation is safer than sheltering in place.
Question 38: A partial evacuation has been ordered for floors 10β15 due to smoke on floor 12. Which action by the FLSD is most appropriate?
- Instruct all occupants to shelter in place until the fire department arrives
- Direct evacuees from floors 10β15 to relocate at least two floors below the affected area (Correct answer)
- Announce a full building evacuation to prevent confusion
- Allow occupants on floors 10β15 to decide individually whether to evacuate
Correct answer: Direct evacuees from floors 10β15 to relocate at least two floors below the affected area
Partial evacuation protocols typically relocate occupants from affected floors to a safe floor at least two floors below the fire floor.
Question 39: When escorting first responders to casualties during an active shooter event, what information should the Fire Life Safety Director provide about wounded victims first?
- Names and employee ID numbers of all victims
- Number of casualties, location, and severity of injuries (Correct answer)
- Insurance and emergency contact details
- A description of the shooter's last known location only
Correct answer: Number of casualties, location, and severity of injuries
First responders prioritize knowing how many casualties there are, where they are located, and the severity of injuries to allocate resources effectively.
Question 40: What is the purpose of a fire department connection (FDC) on a building's sprinkler or standpipe system?
- To serve as a manual shutoff point for building staff
- To provide a test outlet for annual inspections
- To connect the building's BAS to FDNY dispatch systems
- To allow FDNY to supplement system pressure and water supply using pumper apparatus (Correct answer)
Correct answer: To allow FDNY to supplement system pressure and water supply using pumper apparatus
The FDC allows FDNY pumper trucks to inject additional water under pressure into the system when municipal supply alone is insufficient.
Question 41: The FLSD notices that a fire extinguisher has been partially discharged and its pressure gauge is in the 'recharge' zone. The FLSD should:
- Tag the extinguisher as out of service and arrange immediate professional recharging or replacement (Correct answer)
- Mark the extinguisher with tape to indicate it has been used and may be partially effective
- Leave the extinguisher in place until the annual inspection when it can be recharged
- Recharge the extinguisher using a CO2 cartridge from the maintenance room
Correct answer: Tag the extinguisher as out of service and arrange immediate professional recharging or replacement
A partially discharged extinguisher must be immediately taken out of service, tagged, and sent for professional recharging or replacement β a partially charged extinguisher may fail during a fire.
Question 42: Each exit route door must be free of decorations or signs that obscure the __________ of the door.
- Visibility (Correct answer)
- Design
- Attractiveness
- None
Correct answer: Visibility
Each exit route door must be free of decorations or signs that obscure the visibility of the door. This is important to ensure that in the event of an emergency, people can easily locate and access the exit route. Any obstructions or distractions that hinder the visibility of the door can delay or prevent individuals from safely exiting the building. Therefore, it is crucial to prioritize visibility and keep exit route doors clear and unobstructed.
Question 43: When reviewing a new tenant's move-in plans, the FLSD identifies that they intend to store a significant quantity of flammable liquids. The FLSD should:
- Contact the insurance company before allowing any hazardous materials in the building
- Prohibit all flammable liquid storage in office buildings
- Inform the tenant that quantities above certain thresholds require FDNY permits and compliance with hazardous materials storage requirements (Correct answer)
- Allow storage as long as it is in a locked cabinet
Correct answer: Inform the tenant that quantities above certain thresholds require FDNY permits and compliance with hazardous materials storage requirements
Storage of flammable liquids above certain quantities requires FDNY permits and compliance with hazardous materials storage regulations under NYC Fire Code.
Question 44: What does the acronym "FEMA" stand for in the context of fire safety?
- Fire Extinguisher Maintenance Association
- Federal Emergency Management Agency (Correct answer)
- Fire Equipment Manufacturers Association
- Fire Evacuation and Management Association
Correct answer: Federal Emergency Management Agency
FEMA stands for Federal Emergency Management Agency, the U.S. government agency responsible for coordinating responses to disasters and emergencies, including fire-related incidents. The other options are invented names that sound plausible but do not represent any real organization. FEMA is a well-established federal agency and its full name should be memorized.
Question 45: The fire alarm system activates but the building fire pump fails to start automatically. What is the FLSD's immediate priority?
- Notify the fire department and initiate evacuation procedures (Correct answer)
- Instruct maintenance to manually start the pump before calling 911
- Continue monitoring and report the pump failure after the emergency
- Reset the fire pump controller and wait for it to restart
Correct answer: Notify the fire department and initiate evacuation procedures
Life safety takes priority; the FLSD must notify 9-1-1 and begin evacuation while the impaired suppression system is simultaneously reported.
Question 46: An FLSD is at the Fire Command Center when a fire alarm activates. After initiating Phase I recall, arriving FDNY personnel want to use an elevator to reach the floors below the fire. What is the name of the operation that allows firefighters to manually control an elevator from inside the car?
- Phase II Emergency In-Car Operation (Correct answer)
- Independent Service Mode
- Manual Recall Operation
- Phase III Firefighter Override
Correct answer: Phase II Emergency In-Car Operation
Phase II Emergency In-Car Operation allows firefighters to take manual control of a specific elevator car using a key switch inside the car, but only after Phase I recall has been activated. This enables them to transport personnel and equipment to a desired floor while overriding normal hall calls and automatic functions.
Question 47: What does the term 'common path of travel' mean in the context of building egress design that an FLSD must understand?
- The designated evacuation route posted on each floor
- The path from the street to the FDNY command station
- The portion of exit access where occupants must travel in a single direction before reaching a choice of two exits (Correct answer)
- The main lobby corridor that connects all elevators
Correct answer: The portion of exit access where occupants must travel in a single direction before reaching a choice of two exits
Common path of travel is the distance occupants must walk before having a choice of two separate exits; building codes limit this distance to reduce risk.
Question 48: An Area of Rescue Assistance (also called an Area of Refuge) in a high-rise building is designed to:
- Allow firefighters to stage equipment before entering a fire floor
- Serve as a temporary command post for the FLSD during an evacuation
- Provide a fire-protected location where mobility-impaired occupants can wait for assisted evacuation (Correct answer)
- Store evacuation chairs and medical equipment for use during emergencies
Correct answer: Provide a fire-protected location where mobility-impaired occupants can wait for assisted evacuation
An Area of Rescue Assistance is a protected space β typically in a stairwell landing or horizontal exit β where occupants who cannot use the stairs independently can wait safely for firefighter or trained staff assistance. Two-way communication to the fire command station is required.
Question 49: A person collapses in the building lobby and is unresponsive. The FLSD should first:
- Move the person to a safe area before calling for help
- Administer CPR immediately before calling 911
- Wait for FDNY to arrive before beginning any intervention
- Call 911, send someone for an AED, and begin CPR if trained (Correct answer)
Correct answer: Call 911, send someone for an AED, and begin CPR if trained
The correct sequence is to call 911, retrieve the AED, and begin CPR if trained β these steps can happen simultaneously with proper staff coordination.
Question 50: An FLSD must notify the FDNY when which of the following conditions exists?
- A fire drill is scheduled for the following week
- Building occupancy temporarily drops below 50 percent
- A tenant installs new office furniture on a floor
- A fire protection system is out of service for more than four hours (Correct answer)
Correct answer: A fire protection system is out of service for more than four hours
FDNY must be notified when a fire protection system is out of service for more than four hours so that appropriate protective measures can be coordinated.
Question 51: An 'area of refuge' in a high-rise building is defined as:
- The ground floor lobby designated as a safe meeting area
- Any room with a fire-resistant door that can be locked from inside
- A fire-rated space where mobility-impaired occupants can wait safely for rescue assistance (Correct answer)
- A pressurized stairwell available for all occupants to shelter in
Correct answer: A fire-rated space where mobility-impaired occupants can wait safely for rescue assistance
Areas of refuge are fire-rated spaces, typically adjacent to stairwells, equipped with two-way communication to the fire command station, where mobility-impaired occupants await FDNY rescue assistance.
Question 52: The FLSD wants to use visual aids during floor warden training. Which visual aid would be MOST effective?
- A chart showing FDNY response statistics for the building's neighborhood
- A copy of the complete NYC Fire Code
- A photograph of a previous fire in a high-rise building
- A floor plan of the warden's specific floor showing exits, stairwells, alarm devices, and equipment (Correct answer)
Correct answer: A floor plan of the warden's specific floor showing exits, stairwells, alarm devices, and equipment
Floor-specific floor plans with marked exits, stairwells, alarm devices, and equipment are the most practical training tool because they directly reflect what the warden will use during an actual emergency.
Question 53: Under what circumstance is a partial evacuation (selective evacuation) appropriate in a high-rise building?
- When more than half the elevators are operational
- When the FLSD personally assesses the threat as low risk
- When the fire is confirmed to be small and contained to one room
- When directed by FDNY or specified in the approved Fire Safety and Evacuation Plan (Correct answer)
Correct answer: When directed by FDNY or specified in the approved Fire Safety and Evacuation Plan
Selective evacuation is only appropriate when specified by the building's approved Fire Safety and Evacuation Plan or directed by FDNY on scene.
Question 54: What should you do if your clothes catch fire?
- Roll on the ground to extinguish the flames (Correct answer)
- Run outside immediately
- Spray water from a nearby sink
- Hide in a closet
Correct answer: Roll on the ground to extinguish the flames
If your clothes catch fire, you should stop, drop, and roll on the ground to smother the flames by cutting off the fire's oxygen supply. Running outside would fan the flames and make them worse. Spraying water from a sink requires reaching the sink while on fire, which is dangerous. Hiding in a closet provides no benefit and could trap you with the fire.
Question 55: Under the 'Protect' component of the ALICE active shooter protocol, which medical consideration is most important for the Fire Life Safety Director?
- Administer CPR to all barricaded individuals as a precaution
- Unlock all exits to facilitate EMS access
- Position barricaded individuals away from doors to reduce injury if the door is breached (Correct answer)
- Ensure all medications are stored in a central location
Correct answer: Position barricaded individuals away from doors to reduce injury if the door is breached
During barricade (Protect), positioning people away from doors reduces injury risk from ballistic penetration or forced entry.
Question 56: New floor wardens in a high-rise building must receive initial training that covers:
- Advanced firefighting techniques and extinguisher use only
- Emergency procedures, evacuation routes, fire alarm systems, and their specific floor responsibilities (Correct answer)
- NYC Fire Code legal requirements and penalties for non-compliance
- How to operate the building's fire command station
Correct answer: Emergency procedures, evacuation routes, fire alarm systems, and their specific floor responsibilities
Initial floor warden training must cover all emergency procedures, building-specific evacuation routes, fire alarm system basics, and the floor warden's specific responsibilities.
Question 57: A building's Fire Safety Plan references a fire command station located at the main lobby. The lobby is renovated and the fire command station is relocated. Which compliance step must the FLSD take FIRST?
- Post a temporary notice on the old location only
- Wait until the next scheduled plan review cycle
- Update the Fire Safety and Evacuation Plan to reflect the new location and submit to FDNY (Correct answer)
- Conduct a drill to test the new location before updating any documents
Correct answer: Update the Fire Safety and Evacuation Plan to reflect the new location and submit to FDNY
Any change to the fire command station location must be immediately reflected in an updated Fire Safety and Evacuation Plan submitted to FDNY.
Question 58: Which of the following is a required feature of a two-way communication system in an Area of Rescue Assistance?
- A cell phone charging port for the occupant's personal device
- A hands-free intercom connecting the area to the fire command station (Correct answer)
- A direct line to the nearest hospital emergency room
- A visual display showing the current floor's evacuation status
Correct answer: A hands-free intercom connecting the area to the fire command station
Code requires a hands-free, two-way communication system between the Area of Rescue Assistance and the fire command station (lobby or fire control room) so the FLSD can confirm who is waiting and communicate status without the occupant needing to hold a handset.
Question 59: What is the primary purpose of the fire safety plan that the FLSD is required to maintain?
- To satisfy insurance underwriting requirements only
- To provide a comprehensive guide for emergency response and evacuation procedures (Correct answer)
- To document the building's renovation and construction history
- To serve as a marketing document for prospective tenants
Correct answer: To provide a comprehensive guide for emergency response and evacuation procedures
The fire safety plan outlines emergency response procedures, evacuation routes, and staff assignments to guide safe building operations during any fire emergency.
Question 60: What is the purpose of the 'accountability' phase at the end of a fire evacuation drill?
- To confirm all occupants and staff are accounted for and identify anyone missing from the designated assembly area (Correct answer)
- To time how quickly the building can be cleared compared to prior drills
- To assess whether the fire alarm system performed correctly during the drill
- To collect feedback forms from participating tenants about the drill experience
Correct answer: To confirm all occupants and staff are accounted for and identify anyone missing from the designated assembly area
The accountability phase ensures every person is accounted for at the assembly area, which is a critical life-safety function that mirrors real emergency procedures.
Question 61: Which of the following is considered a manual fire alarm initiating device?
- Sprinkler water flow switch
- Pull station (Correct answer)
- Heat detector
- Smoke detector
Correct answer: Pull station
A manual pull station requires human intervention to activate the fire alarm system. Smoke detectors, heat detectors, and water flow switches are all automatic initiating devices that activate when they sense specific conditions related to a fire, such as smoke, high temperature, or water movement in the sprinkler pipes.
Question 62: Which of the following must be recorded in the FLSD fire safety log after each fire alarm activation?
- Time of alarm, cause of activation, and actions taken (Correct answer)
- Elevator inspection certificates for the day
- Building temperature and humidity readings at time of alarm
- Names of all tenants present in the building at the time
Correct answer: Time of alarm, cause of activation, and actions taken
The fire safety log must document the time, cause, and all response actions for every alarm activation to create an accurate and reviewable incident record.
Question 63: An FLSD finds a self-closing fire door propped open with a wedge. What action must be taken?
- Schedule a repair for the following month
- Close the door immediately and investigate why it was propped open (Correct answer)
- Leave it open if the area is currently occupied
- Remove the door temporarily from service
Correct answer: Close the door immediately and investigate why it was propped open
Fire doors must never be propped open because they are critical passive barriers against fire and smoke spread, and the FLSD must close them at once.
Question 64: An occupant with a mobility impairment cannot use the stairwell during an evacuation. Where should the FLSD direct them to wait?
- In the main lobby elevator bank
- In the nearest restroom
- On the roof for helicopter access
- At an Area of Rescue Assistance (ARA) on their floor (Correct answer)
Correct answer: At an Area of Rescue Assistance (ARA) on their floor
Areas of Rescue Assistance are designated safe zones where mobility-impaired occupants wait for FDNY assistance during evacuation.
Question 65: An occupant trapped on the 35th floor during a fire, unable to use stairwells, should:
- Shelter in a room, seal gaps under the door, signal from the window, and call 911 to report their location (Correct answer)
- Use the elevator as a last resort to escape
- Jump from the window onto the fire truck aerial ladder
- Attempt to rappel down the exterior of the building
Correct answer: Shelter in a room, seal gaps under the door, signal from the window, and call 911 to report their location
A trapped occupant should shelter in place β seal smoke gaps under the door, call 911 with their exact floor and room number, and signal from the window to alert rescuers of their location.
Question 66: When conducting a fire drill in a high-rise building, what is the primary purpose of a 'silent drill'?
- To test alarm systems without notifying occupants in advance
- To assess the Fire Life Safety Director's personal response time
- To practice evacuation procedures without disturbing neighboring tenants
- To evaluate staff response without triggering audible alarms for all floors (Correct answer)
Correct answer: To evaluate staff response without triggering audible alarms for all floors
Silent drills allow the FLSD to evaluate staff performance and response procedures without activating the full alarm system for every floor, minimizing disruption while still testing readiness.
Question 67: Under FDNY regulations, what is the minimum frequency for conducting fire drills in a Class E (high-rise office) building?
- Quarterly
- Annually
- Semi-annually (twice per year) (Correct answer)
- Monthly
Correct answer: Semi-annually (twice per year)
Class E high-rise office buildings are required to conduct fire drills at least twice per year (semi-annually) under FDNY regulations.
Question 68: Under NFPA 72, what is the maximum allowable distance between heat detectors in a smooth-ceiling area with a standard 10-foot ceiling height?
- 50 feet between detectors in any direction (Correct answer)
- 75 feet between detectors in any direction
- 20 feet between detectors in any direction
- 30 feet between detectors in any direction
Correct answer: 50 feet between detectors in any direction
NFPA 72 specifies that heat detectors on smooth ceilings up to 10 feet high may be spaced no more than 50 feet apart in any direction.
Question 69: A new security guard will be stationed at the building lobby. The FLSD should ensure the guard is trained on:
- How to conduct building inspections for fire code violations
- The complete Fire Safety Plan in full detail
- How to recognize fire alarm signals, assist with building access for FDNY, and perform basic emergency notification duties (Correct answer)
- Advanced firefighting techniques and extinguisher use
Correct answer: How to recognize fire alarm signals, assist with building access for FDNY, and perform basic emergency notification duties
Security guards in high-rise buildings play a critical supporting role and must be trained to recognize alarms, facilitate FDNY access, and perform notification duties.
Question 70: A building decides to conduct an unannounced fire drill. What is the FLSD's responsibility?
- Notify FDNY 30 days before any unannounced drill
- Ensure floor wardens know it is a drill even if tenants are not pre-notified (Correct answer)
- Obtain written consent from all tenants before conducting the drill
- Cancel the drill if any tenants object to the unannounced format
Correct answer: Ensure floor wardens know it is a drill even if tenants are not pre-notified
While tenants may not be pre-notified in an unannounced drill, floor wardens must know it is a drill so they can properly manage the evacuation and the safety of occupants.
Question 71: According to NYC Fire Code, occupants in a high-rise should use a stairwell other than their normal stairwell when:
- They are on odd-numbered floors versus even-numbered floors
- The building has more than 500 occupants on their floor
- They have mobility impairments and need a wider stairwell
- The normally used stairwell has smoke, is blocked, or is directed by FDNY (Correct answer)
Correct answer: The normally used stairwell has smoke, is blocked, or is directed by FDNY
Occupants should use their designated stairwell unless it is compromised by smoke, blocked by hazards, or FDNY redirects them to a specific alternate stairwell.
Question 72: Which of the following must be documented in the FLS Logbook?
- Records of all fire drills and FLS staff training sessions. (Correct answer)
- Daily start and end times for all building maintenance staff.
- The personal contact information of all building tenants.
- A list of all scheduled deliveries to the building for the week.
Correct answer: Records of all fire drills and FLS staff training sessions.
The FLS Logbook is a formal record of compliance with fire safety regulations. It must contain entries for all fire drills, staff training, fire incidents, and the identification of on-duty FLS staff. The other options are related to general building management or security, but are not required components of the official FLS Logbook.
Question 73: A building's Fire Safety/Evacuation Plan (FS/EP) includes a 'Special Needs Registry.' What is this registry's primary purpose?
- To record all past fire drill participation rates by floor
- To track employees who have received CPR/AED certification
- To document occupants who may require assistance during evacuation so wardens and FDNY are prepared in advance (Correct answer)
- To list contractors who have access to mechanical rooms for maintenance
Correct answer: To document occupants who may require assistance during evacuation so wardens and FDNY are prepared in advance
The Special Needs Registry is a pre-emergency planning tool that identifies occupants (permanent or temporary) who may need evacuation assistance β due to mobility, sensory, or cognitive impairments β so that floor wardens can be assigned and FDNY can be immediately informed during an incident.
Question 74: What is the first action an FLSD should take during a building-wide power outage?
- Notify the building management and maintenance teams. (Correct answer)
- Activate backup lighting and generator systems.
- Order an immediate evacuation of the building.
- Confirm the operation of life safety systems, including fire alarms and sprinklers. (Correct answer)
Correct answer: Notify the building management and maintenance teams.
During a building-wide power outage, the FLSD's first action should be to notify the relevant building management and maintenance teams. These teams are responsible for assessing the cause, initiating repairs, and activating backup systems. While confirming life safety systems is vital, informing those who can restore power and manage the technical response is the initial coordination step.
Question 75: A FLSD notices that non-English-speaking occupants struggled to understand evacuation instructions during a drill. What is the BEST solution?
- Provide multilingual fire safety materials and assign bilingual floor wardens where possible (Correct answer)
- Require all occupants to take English language classes
- Use louder alarm signals to overcome language barriers
- Post evacuation signs only in English since it is the official language
Correct answer: Provide multilingual fire safety materials and assign bilingual floor wardens where possible
Providing fire safety information in multiple languages and using bilingual wardens ensures all occupants can understand and follow evacuation procedures.
Question 76: A fire alarm control panel shows a 'trouble' signal. This indicates:
- The system is in test mode and should be ignored
- All detectors have been manually silenced
- An active fire has been detected in the building
- A system fault β wiring issue, power problem, or device malfunction (Correct answer)
Correct answer: A system fault β wiring issue, power problem, or device malfunction
A 'trouble' signal indicates a fault in the fire alarm system itself β such as a wiring break, low battery, or detector malfunction β not an active fire condition.
Question 77: A fire alarm system is interconnected with the building's HVAC system. Upon the activation of a duct smoke detector in the main supply ductwork for the 15th floor, what is the expected automatic action of the associated HVAC unit?
- The unit will switch to a special filtration mode.
- The unit will increase airflow to clear the smoke.
- The unit will reverse airflow to pull smoke back to the detector.
- The unit will shut down to prevent the distribution of smoke. (Correct answer)
Correct answer: The unit will shut down to prevent the distribution of smoke.
A primary function of duct smoke detectors is to prevent the spread of smoke through the HVAC system. When a detector activates, it sends a signal to the fire alarm panel, which in turn signals the air handling unit to shut down, stopping the fan and closing dampers to contain the smoke.
Question 78: Which type of sprinkler head responds fastest to heat and is typically used in high-hazard areas?
- Dry pipe sprinkler
- Standard response sprinkler (RTI > 80)
- Quick response sprinkler (RTI β€ 50) (Correct answer)
- Extended coverage sprinkler
Correct answer: Quick response sprinkler (RTI β€ 50)
Quick response sprinklers have a lower Response Time Index (RTI β€ 50) and activate faster than standard sprinklers, providing earlier suppression in high-hazard environments.
Question 79: A fire emergency occurs and the primary stairwell designated for evacuation is blocked by heavy smoke. What should the FLSD instruct floor wardens to do?
- Allow occupants to use the elevator since the stairwell is unusable
- Have occupants wait in the smoke-filled stairwell until the fire department clears it
- Direct occupants to use an alternate egress stairwell and notify the fire department of the blocked stairwell (Correct answer)
- Instruct occupants to return to their offices and shelter in place indefinitely
Correct answer: Direct occupants to use an alternate egress stairwell and notify the fire department of the blocked stairwell
Alternate stairwells must be used when the primary route is compromised, and the fire department must be informed immediately of the blocked egress path.
Question 80: Under NYC Building Code, what is the minimum fire resistance rating required for ductwork penetrations through a 2-hour fire-rated floor/ceiling assembly without a fire damper?
- The penetration is never permitted without a fire damper
- HVAC ducts are exempt from fire rating requirements at floor penetrations
- 1-hour rating for the duct itself
- The duct must be wrapped with 2-hour rated enclosure (Correct answer)
Correct answer: The duct must be wrapped with 2-hour rated enclosure
Where fire dampers are not provided, ductwork penetrating rated assemblies must be enclosed in a shaft or wrapped with materials providing equivalent fire resistance.
Question 81: A fire alarm is activated on the 22nd floor of a 40-story building. Which floors should receive a relocation signal directing occupants to move to a lower floor?
- Floors 21 through 24
- Floors 20 through 24 (Correct answer)
- Only floor 22
- Floors 20 through 22
Correct answer: Floors 20 through 24
Relocation typically involves the fire floor and two floors above and below to create a buffer zone, though exact protocols may vary by building plan.
Question 82: During a high-rise fire, occupants should be instructed to check a closed door before opening it by:
- Using the back of their hand to feel the door and doorknob for heat (Correct answer)
- Smelling for smoke at the door gap
- Looking under the door for visible flames
- Opening the door a crack and checking for smoke
Correct answer: Using the back of their hand to feel the door and doorknob for heat
Before opening any door during a fire, feel it with the back of your hand β if it is hot, the fire may be on the other side. The back of the hand is used because palm burns can impair grip.
Question 83: After a complete building evacuation to the designated assembly area, what is the FLSD's most important life-safety function before FDNY clears the building for re-entry?
- Contact building management and insurance carriers to begin damage documentation
- Coordinate with floor wardens to compile floor-by-floor headcounts and immediately report any unaccounted persons to FDNY incident command (Correct answer)
- Release floor wardens from duty and permit occupants to self-organize at the assembly point
- Conduct a personal re-entry sweep of all stairwells to confirm they are clear
Correct answer: Coordinate with floor wardens to compile floor-by-floor headcounts and immediately report any unaccounted persons to FDNY incident command
Accurate headcounts compiled through the floor warden network allow the FLSD to tell FDNY exactly who may still be in the building. This information directly shapes the firefighter search-and-rescue priorities and can save lives.
Question 84: After FDNY declares 'all clear' and the building is ready for re-occupancy, the FLSD should:
- Conduct a systematic re-entry, check the building for hazards, and brief occupants before they return (Correct answer)
- Immediately allow all occupants back into the building without further checks
- Reset the fire alarm system and leave the rest to building management
- Contact the building owner first and await authorization to re-open
Correct answer: Conduct a systematic re-entry, check the building for hazards, and brief occupants before they return
Re-entry after FDNY all-clear should be systematic β the FLSD checks for hazards (water damage, compromised structure), briefs floor wardens, and ensures safe re-occupancy before opening the building.
Question 85: An FLSD is notified of a non-fire emergency, such as a suspicious package found in the lobby. Which of the following actions represents the most appropriate initial response strategy?
- Immediately direct all building occupants to the primary evacuation assembly area.
- Consult the building's Emergency Action Plan (EAP) to determine the correct procedure. (Correct answer)
- Activate the building's fire alarm system to ensure a rapid evacuation.
- Attempt to move the suspicious package to an isolated area outside the building.
Correct answer: Consult the building's Emergency Action Plan (EAP) to determine the correct procedure.
The Emergency Action Plan (EAP) is a distinct set of procedures for non-fire emergencies. Activating the fire alarm is incorrect as it could lead to inappropriate actions by occupants (e.g., evacuating when sheltering-in-place is required). The FLSD must first consult the EAP to determine the specific threat and the corresponding planned response, which could be sheltering-in-place, in-building relocation, or a partial/full evacuation.
Question 86: When training staff on the use of a portable fire extinguisher, the FLSD should teach the PASS technique. What does the letter 'S' stand for?
- Spray
- Sweep (Correct answer)
- Squeeze
- Secure
Correct answer: Sweep
In the PASS technique, 'S' stands for Sweep β moving the extinguisher nozzle from side to side at the base of the fire.
Question 87: Which of the following spaces typically presents the highest fire load in a commercial high-rise building?
- Elevator machine rooms
- Server rooms and data centers (Correct answer)
- Lobby entrance areas
- Stairwell landings
Correct answer: Server rooms and data centers
Server rooms and data centers contain dense concentrations of electronic equipment and cabling, representing a significant combustible fire load.
Question 88: When FDNY arrives at a building during a medical emergency, the FLSD should:
- Call 911 again to update them on the patient's condition
- Activate the fire alarm system to clear a path for paramedics
- Stand aside and let FDNY handle everything independently
- Meet FDNY at the fire command station and provide floor and patient location (Correct answer)
Correct answer: Meet FDNY at the fire command station and provide floor and patient location
The FLSD must meet FDNY at the fire command station, provide the exact location of the medical emergency, and facilitate elevator access for emergency responders.
Question 89: A fire is confirmed on the 20th floor of a 40-story building. Which floors should the FLSD prioritize for evacuation first?
- The entire building simultaneously
- Only the fire floor
- The fire floor, the floor above, and the floor below (Correct answer)
- All floors above the fire floor only
Correct answer: The fire floor, the floor above, and the floor below
Standard high-rise evacuation protocol prioritizes the fire floor and the floors immediately above and below it due to the greatest immediate danger.
Question 90: In a dry pipe sprinkler system, what substance fills the pipes in place of water?
- Argon
- Halon gas
- Carbon dioxide
- Pressurized air or nitrogen (Correct answer)
Correct answer: Pressurized air or nitrogen
Dry pipe systems use pressurized air or nitrogen to hold a clapper valve closed, keeping water out of the pipes until a sprinkler head opens.
Question 91: A tenant calls the fire command station to report smoke coming from under a closed office door on the 8th floor. No alarm has activated. What is the FLSD's first action?
- Wait for the alarm system to activate before taking any action
- Send a maintenance worker to open the door and investigate
- Announce a building-wide evacuation immediately
- Call 9-1-1, initiate investigation, and prepare for possible evacuation (Correct answer)
Correct answer: Call 9-1-1, initiate investigation, and prepare for possible evacuation
A report of smoke is a life-safety threat requiring immediate notification of 9-1-1 and preparation for evacuation, even without an alarm activation.
Question 92: Which NFPA standard governs the installation, testing, and maintenance of fire alarm and signaling systems in the United States?
- NFPA 72 (Correct answer)
- NFPA 101
- NFPA 25
- NFPA 13
Correct answer: NFPA 72
NFPA 72, the National Fire Alarm and Signaling Code, is the primary standard governing fire alarm system installation, testing, and maintenance.
Question 93: Besides fire emergencies, the Fire Life Safety Director is also responsible for implementing the Emergency Action Plan for which of the following scenarios?
- Scheduled elevator maintenance.
- Power outages and active shooter incidents. (Correct answer)
- Routine water shutoffs for plumbing repairs.
- Tenant disputes and noise complaints.
Correct answer: Power outages and active shooter incidents.
The FLSD's role has expanded to include non-fire emergencies, which are covered under the Emergency Action Plan (EAP). These include serious situations that threaten building occupants, such as power outages, natural disasters, explosions, biological threats, and active shooter incidents. The other options are building management or maintenance issues, not EAP events.
Question 94: A Class II standpipe system provides 1.5-inch hose stations intended for use by which group?
- Fire department personnel exclusively
- Security personnel during off-hours only
- Building occupants for initial fire attack (Correct answer)
- Trained fire brigades with full PPE only
Correct answer: Building occupants for initial fire attack
Class II standpipe systems are designed for use by building occupants to attempt initial fire suppression before the fire department arrives, using pre-connected 1.5-inch hose lines.
Question 95: Under NYC fire code, what action must an FLSD take when the fire alarm system goes into a 'supervisory' signal state?
- Immediately evacuate the building
- Activate the building's emergency lighting system
- Silence the panel and resume normal operations
- Investigate the cause and notify the fire alarm monitoring company (Correct answer)
Correct answer: Investigate the cause and notify the fire alarm monitoring company
A supervisory signal indicates a monitored system (e.g., sprinkler valve) may be impaired and requires investigation and notification of the monitoring company.
Question 96: A flood occurs in the basement mechanical room. The FLSD should be concerned about which immediate safety hazard?
- Elevator shaft flooding affecting Phase I recall
- Electrical panel flooding causing electrocution hazard and potential fire (Correct answer)
- Sprinkler system water supply interruption
- Water pressure damage to the standpipe system
Correct answer: Electrical panel flooding causing electrocution hazard and potential fire
Flooding near electrical panels, motors, and service equipment creates electrocution hazards and can cause electrical fires β this is the most immediate life safety concern.
Question 97: Which of the following best describes the purpose of a pre-fire plan for a high-rise building?
- A document listing the building owner's insurance coverage details
- A marketing plan for fire safety equipment vendors
- A schedule for annual fire drills only
- A document provided to the fire department detailing building layout, hazards, and emergency systems (Correct answer)
Correct answer: A document provided to the fire department detailing building layout, hazards, and emergency systems
A pre-fire plan gives responding firefighters critical information about building layout, occupancy, hazards, and the location of fire protection systems.
Question 98: In a high-rise building, a fire alarm is activated on the 10th floor. Standard procedure for a phased evacuation typically requires a public address system announcement directing the occupants of which floors to begin evacuation?
- The 10th floor, and the two floors above and two floors below (8, 9, 10, 11, 12).
- The 10th floor and the floor immediately above and below (9, 10, 11). (Correct answer)
- Only the 10th floor.
- All floors above the 10th floor.
Correct answer: The 10th floor and the floor immediately above and below (9, 10, 11).
While specific plans can vary, a common phased evacuation strategy in high-rise buildings is to evacuate the fire floor (the floor of alarm) plus the floors immediately above and below it. This approach minimizes the number of people in the stairwells at one time, preventing overcrowding and allowing for a more controlled evacuation. The occupants of other floors are typically instructed to stand by for further instructions.
Question 99: During a high-rise evacuation, the FLSD learns that three mobility-impaired occupants are waiting in Areas of Rescue Assistance on floors 18 and 24. What is the FLSD's primary duty regarding these individuals?
- Advise them to move to the nearest corridor and wait for smoke to clear
- Instruct available staff to carry them down the stairwell immediately
- Direct them to use a passenger elevator to descend to the lobby
- Record their exact locations and floor numbers and relay that information to FDNY upon arrival (Correct answer)
Correct answer: Record their exact locations and floor numbers and relay that information to FDNY upon arrival
The FLSD must maintain a real-time log of occupants sheltering in Areas of Rescue Assistance and provide that information to the FDNY incident commander so firefighters can prioritize rescue. Unauthorized attempts to carry occupants down stairs can cause injury and create additional hazards.
Question 100: Which communication method should the FLSD use to relay instructions to floor wardens during a high-rise fire emergency when normal phones are inoperable?
- Personal cell phones only
- Shouting from the stairwell
- The building's fire command station two-way voice communication system (Correct answer)
- Email or text message
Correct answer: The building's fire command station two-way voice communication system
High-rise buildings are required to have a two-way voice communication system at the fire command station for use during emergencies.
FDNY Fire Life Safety Director (F-85/F-89)
This certification is required for individuals responsible for implementing and managing fire safety plans and emergency procedures in high-rise and other designated buildings in New York City, ensuring the safety of occupants during emergencies.
Exam Rules
- You can skip questions and return to them later
- Flag questions for review before submitting
- No feedback shown until you submit the entire exam
- Unanswered questions count as wrong β answer everything
- 10 pretest questions are mixed in and don't affect your score
- Timer auto-submits when time runs out
- Your progress is auto-saved every 30 seconds