Fire and Life Safety Flashcards

6 cards from real CHFM practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 6 Fire and Life Safety flashcards as text
  1. A hospital's fire sprinkler system in a non-patient care wing is taken out of service for a planned repair that is expected to last 8 hours. According to The Joint Commission and NFPA standards, which of the following is required?

    Answer: Notify the local fire department and implement a fire watch.

    When a fire alarm or suppression system is out of service for more than 4 hours in a 24-hour period in an occupied building, Interim Life Safety Measures (ILSM) must be implemented. A key component of ILSM is notifying the local fire department and initiating a fire watch to patrol the affected areas.

  2. According to NFPA 101, Life Safety Code®, what is the minimum frequency for conducting fire drills in a hospital?

    Answer: Once per quarter on each shift.

    Both NFPA 101 and The Joint Commission require healthcare occupancies to conduct fire drills quarterly on each shift to familiarize all personnel with signals and emergency procedures under varied conditions.

  3. A facility manager is reviewing the design for a new patient care unit. Per the NFPA 101, Life Safety Code®, which of the following is a primary requirement for a smoke compartment?

    Answer: It must not exceed a maximum square footage and travel distance to a smoke barrier door.

    NFPA 101 specifies requirements for smoke compartments to limit the spread of smoke. These requirements include a maximum area (traditionally 22,500 sq ft, though recent editions allow up to 40,000 sq ft under specific conditions) and a maximum travel distance (typically 200 ft) from any point within the compartment to a door in a smoke barrier.

  4. During the annual inspection of fire door assemblies, which of the following findings would be considered a deficiency according to NFPA 80, Standard for Fire Doors and Other Opening Protectives?

    Answer: An unapproved magnetic holder is installed, preventing the door from self-closing.

    NFPA 80 requires fire doors to be self-closing and positive-latching. Any field modification or auxiliary hardware, such as an unapproved magnetic hold-open device, that interferes with the door's ability to close and latch automatically is a significant deficiency.

  5. A healthcare facility manager must ensure that the medical gas and vacuum systems are maintained safely. Which NFPA standard provides the primary risk-based criteria for these systems, covering their performance, installation, and maintenance to reduce fire and explosion risks?

    Answer: NFPA 99 - Health Care Facilities Code

    NFPA 99, Health Care Facilities Code, establishes criteria for levels of health care services or systems based on risk to the patients, staff, or visitors in health care facilities to minimize the hazards of fire, explosion, and electricity. It specifically covers medical gas and vacuum systems.

  6. Which of the following is the primary purpose of conducting a fire pump's weekly "no-flow" or "churn" test as required by NFPA 25?

    Answer: To confirm the pump will start automatically and run without overheating or showing signs of distress.

    The weekly no-flow (churn) test, as specified in NFPA 25, is primarily intended to verify the automatic start of the pump and ensure its components operate correctly without signs of overheating, unusual vibration, or leaks. It's a test of readiness, not of full hydraulic performance.

How this page was made: written with AI tools and published by Nathan Beja, founder of Practice Test Geeks, who is responsible for its content. Exam facts are checked against the official sources listed below. Not reviewed by a subject-matter expert. Editorial policy