← All CFM Flashcard Decks

Hazardous Materials & Building Safety Flashcards

28 cards from real CFM practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 20 Hazardous Materials & Building Safety flashcards as text
  1. Under NFPA 30, a liquid with a flash point of 85°F is classified as which class?

    Answer: Class IC

    Class IC liquids have flash points at or above 73°F and below 100°F.

  2. On an NFPA 704 diamond, what does the yellow quadrant indicate?

    Answer: Instability (reactivity)

    The yellow quadrant rates instability, from 0 (stable) to 4 (may detonate at normal conditions).

  3. Which IBC occupancy group applies to a building storing materials that pose a detonation hazard, such as Division 1.1 explosives above the maximum allowable quantity?

    Answer: H-1

    Group H-1 covers materials that present a detonation hazard.

  4. In the Emergency Response Guidebook (ERG), which colored section lists initial isolation and protective action distances?

    Answer: Green pages

    Green pages give isolation and protective action distances for TIH and water-reactive materials.

  5. What is the maximum capacity of an approved safety can for flammable liquids under NFPA 30?

    Answer: 5 gallons

    Safety cans are limited to 5 gallons (19 L) and have a spring-closing lid and flame arrester.

  6. Per the IBC, an interior exit stairway connecting four or more stories must be enclosed with construction having what minimum fire-resistance rating?

    Answer: 2 hours

    Exit enclosures connecting four or more stories need 2-hour fire-resistance-rated construction.

  7. Which SDS section gives exposure limits and required personal protective equipment?

    Answer: Section 8

    Section 8 (Exposure Controls/Personal Protection) lists PELs, TLVs, engineering controls, and PPE.

  8. Under the IFC, how many control areas are permitted on the first story above grade plane, and at what percentage of the maximum allowable quantity?

    Answer: 4 control areas at 100%

    IFC Table 5003.8.3.1 allows 4 control areas at 100% MAQ on the first floor.

  9. What is the main feature that sets a fire wall apart from a fire barrier under the IBC?

    Answer: A fire wall must stay structurally stable under fire conditions so that collapse on either side does not bring it down

    Fire walls create separate buildings and must stay standing if construction on either side collapses.

  10. Which DOT hazard class covers oxidizers and organic peroxides?

    Answer: Class 5

    DOT Class 5 covers oxidizers (5.1) and organic peroxides (5.2).

  11. Under the IFC, secondary containment for indoor hazardous liquid storage must hold the volume of the largest vessel plus the sprinkler discharge for how long?

    Answer: 20 minutes

    The IFC requires the largest container's volume plus 20 minutes of fire-extinguishing system discharge over the area.

  12. A material that ignites spontaneously in air at or below 130°F (54.4°C) is classified as:

    Answer: Pyrophoric

    The IFC and NFPA 400 define pyrophoric materials as those that ignite spontaneously in air at or below 130°F.

  13. How must stored oxygen cylinders be separated from flammable gas cylinders when no barrier is present?

    Answer: 20 feet

    Oxygen must be 20 feet from fuel gas cylinders, or separated by a noncombustible barrier at least 5 feet high with a 1/2-hour rating.

  14. Which EPCRA section requires facilities to submit annual Tier II hazardous chemical inventory reports to the SERC, LEPC, and local fire department?

    Answer: Section 312

    EPCRA Section 312 requires annual Tier II inventory reporting.

  15. Which IBC occupancy classification applies to semiconductor fabrication facilities that use hazardous production materials (HPM)?

    Answer: H-5

    Group H-5 covers semiconductor fabrication and comparable R&D facilities that use HPM.

  16. Under NFPA 30, what is the maximum amount of Class I and Class II liquids allowed in a single approved flammable liquid storage cabinet?

    Answer: 60 gallons

    A cabinet may hold up to 60 gallons of Class I and II liquids, or 120 gallons of Class I, II, and IIIA combined.

  17. A gas with a vapor density of 1.5, such as propane, released inside a building will most likely:

    Answer: Collect in low areas such as basements and pits

    Gases with a vapor density greater than 1 are heavier than air and settle in low spots.

  18. Which GHS pictogram identifies an oxidizer?

    Answer: Flame over circle

    The flame-over-circle pictogram marks oxidizing gases, liquids, and solids.

  19. What does a fire marshal require during transfer of Class I liquids between metal containers to prevent static ignition?

    Answer: Bonding and grounding

    Bonding equalizes potential between the containers and grounding drains static to earth, preventing sparks.

  20. Under the IFC, how wide must an unobstructed fire apparatus access road be, at minimum?

    Answer: 20 feet

    IFC 503.2.1 requires at least 20 feet of unobstructed width and 13 ft 6 in of vertical clearance.

Written and edited by , founder of Practice Test Geeks, with AI assistance. Exam facts are checked against the official sources linked below. Editorial policy

Sources & references

Exam facts on this page (fees, format, dates, passing scores) are checked against these official sources; the date is our last check. Editorial policy

  1. iccsafe.org — Retake policy, exam format, time limit, registration, test delivery, eligibility, exam information · verified Nov 2026
  2. support.iccsafe.org — Renewal, score release, passing score · verified Nov 2026
  3. cdn-www-v2.iccsafe.org — Score validity · verified Nov 2026
  4. shop.iccsafe.org — Fees, registration deadline · verified Nov 2026