← All CFM Flashcard Decks

Fire Prevention & Code Enforcement Flashcards

28 cards from real CFM practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 20 Fire Prevention & Code Enforcement flashcards as text
  1. Under NFPA 1730, how often should occupancies classified as high-risk generally be inspected?

    Answer: Annually

    NFPA 1730 recommends annual inspections for high-risk occupancies, biennial for moderate-risk, and triennial for low-risk.

  2. Which U.S. Supreme Court case established that a fire inspector generally needs an administrative warrant to inspect a commercial property without the owner's consent?

    Answer: See v. City of Seattle

    See v. City of Seattle (1967) extended the administrative warrant requirement of Camara to commercial premises.

  3. Under the IFC, when an automatic sprinkler system is out of service for more than how many hours in a 24-hour period, the fire code official must be notified and the building evacuated or a fire watch provided?

    Answer: 10 hours

    IFC 901.7 sets 10 hours in a 24-hour period for sprinkler impairments and 4 hours for fire alarm impairments.

  4. An inspector finds combustible storage stacked directly beneath sprinkler deflectors in a warehouse. What minimum clearance is typically required below the deflectors?

    Answer: 18 inches

    A minimum 18-inch clearance below sprinkler deflectors is required so the discharge pattern is not obstructed.

  5. Which IFC permit type is required to conduct an ongoing activity such as storing hazardous materials or operating a place of assembly?

    Answer: Operational permit

    The IFC distinguishes operational permits for ongoing activities from construction permits for installing or modifying systems.

  6. A notice of violation issued by a fire marshal should, at a minimum, include which of the following elements?

    Answer: A description of the violation, the code section, a correction deadline, and appeal rights

    Due process requires the notice to identify the violation, cite the code, give time to correct, and explain the right to appeal.

  7. Under the IFC, what is the minimum unobstructed width of a fire apparatus access road?

    Answer: 20 feet

    IFC requires fire apparatus access roads to have at least 20 feet of unobstructed width and 13 feet 6 inches of vertical clearance.

  8. Per NFPA 96, how often should exhaust systems serving solid-fuel cooking operations be inspected for grease buildup?

    Answer: Monthly

    NFPA 96 requires monthly inspection for systems serving solid-fuel cooking operations.

  9. Under the NFPA flammable liquid classification, a liquid with a flash point below 73°F and a boiling point below 100°F is classified as which class?

    Answer: Class IA

    Class IA liquids have a flash point below 73°F and a boiling point below 100°F, making them the most hazardous flammable liquids.

  10. During a hot work permit inspection under NFPA 51B, combustible materials generally must be relocated at least how far from the work area?

    Answer: 35 feet

    NFPA 51B uses a 35-foot radius for relocating or protecting combustibles around hot work.

  11. An inspector observes a fire door held open with a wooden wedge in a hospital corridor. What is the correct code interpretation?

    Answer: A violation; fire doors may be held open only by approved devices that release on smoke detection or fire alarm activation

    NFPA 80 and the IFC prohibit wedging fire doors open; only listed hold-open devices that release automatically are allowed.

  12. NFPA 80 requires fire door assemblies to be inspected and tested at what minimum frequency?

    Answer: Annually

    NFPA 80 requires fire door assemblies to be inspected and tested at least annually, with written records kept.

  13. Under ASTM E84, interior finish materials with a flame spread index of 0-25 are classified as which class?

    Answer: Class A

    Class A is 0-25, Class B is 26-75, and Class C is 76-200 flame spread index.

  14. Which of the five E's of community risk reduction involves using fines, citations, and code compliance actions?

    Answer: Enforcement

    Enforcement uses legal and regulatory tools such as codes, citations, and penalties to reduce risk.

  15. Under the IFC, panic or fire exit hardware is required on swinging egress doors with locks or latches in Group A and Group E occupancies with an occupant load of at least:

    Answer: 50

    IFC/IBC require panic hardware in Group A and E occupancies when the occupant load is 50 or more.

  16. Using IBC/IFC occupant load factors, what is the factor for an unconcentrated assembly area with tables and chairs?

    Answer: 15 net sq ft per person

    Unconcentrated assembly (tables and chairs) uses 15 net square feet per occupant.

  17. Emergency lighting for means of egress must typically provide illumination for at least how long after loss of normal power?

    Answer: 90 minutes

    NFPA 101 and the IFC require emergency lighting to operate for a minimum of 90 minutes.

  18. In a fully sprinklered building, the minimum separation between two required exits is generally at least what fraction of the overall diagonal of the area served?

    Answer: One-third

    The exit separation rule is one-half the diagonal, reduced to one-third when the building is fully sprinklered.

  19. An inspector finds extension cords run through a wall to permanently power a vending machine. What is the correct action?

    Answer: Cite the violation, since extension cords may not substitute for permanent wiring

    The IFC prohibits extension cords as a substitute for permanent wiring and prohibits running them through walls, ceilings, or floors.

  20. Under NFPA 72, smoke alarms in dwelling units must be replaced no later than how many years from their date of manufacture?

    Answer: 10 years

    NFPA 72 requires smoke alarms to be replaced 10 years from the manufacture date or sooner if they fail testing.

Written and edited by , founder of Practice Test Geeks, with AI assistance. Exam facts are checked against the official sources linked below. Editorial policy

Sources & references

Exam facts on this page (fees, format, dates, passing scores) are checked against these official sources; the date is our last check. Editorial policy

  1. iccsafe.org — Retake policy, exam format, time limit, registration, test delivery, eligibility, exam information · verified Nov 2026
  2. support.iccsafe.org — Renewal, score release, passing score · verified Nov 2026
  3. cdn-www-v2.iccsafe.org — Score validity · verified Nov 2026
  4. shop.iccsafe.org — Fees, registration deadline · verified Nov 2026