  1. A technician measures a compressor's amp draw and finds it is above the rated full-load amps (FLA). Which condition would most likely cause this?

    Answer: High condensing temperature due to poor heat rejection

    High condensing temperatures increase the pressure ratio the compressor must work against, forcing it to draw more current than its rated FLA.

  2. When evacuating a refrigeration system, the vacuum pump should be connected to:

    Answer: Both the high and low side service ports simultaneously

    Connecting to both service ports ensures a faster, more complete evacuation by removing moisture and non-condensables from both sides of the system.

  3. What micron level must be achieved and held during system evacuation before charging with refrigerant?

    Answer: 500 microns or lower

    Industry standards require pulling the system down to 500 microns or lower and verifying the level holds to confirm adequate moisture removal and leak integrity.

  4. A homeowner reports that the AC runs constantly but never reaches the set temperature. After inspection, the technician finds the evaporator coil is clean and airflow is good. The NEXT diagnostic step should be:

    Answer: Measure system operating pressures and temperatures

    Measuring operating pressures and temperatures provides the data needed to diagnose whether the issue is refrigerant charge, metering device, or compressor performance.

  5. Which tool is used to verify that a crankcase heater on a compressor is functioning properly?

    Answer: Clamp-style ammeter or infrared thermometer

    A clamp-style ammeter measures the small current draw of the crankcase heater, while an infrared thermometer confirms the heater is producing heat at the compressor base.

  6. What condition is indicated when the liquid line feels warm to the touch near the condenser on a properly charged system on a hot day?

    Answer: This is normal — the liquid line should be warm, carrying high-pressure liquid

    The liquid line carries high-pressure, warm liquid refrigerant from the condenser and will naturally feel warm to the touch under normal operation.

  7. A technician is servicing a heat pump in heating mode. Which component directs refrigerant flow to reverse the heating and cooling cycle?

    Answer: Reversing (four-way) valve

    The reversing valve (four-way valve) redirects refrigerant flow so the outdoor coil acts as the evaporator and the indoor coil acts as the condenser during heating mode.