Installation and Evacuation Procedures Flashcards

21 cards from real Air Conditioning Repair practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 20 Installation and Evacuation Procedures flashcards as text
  1. What is the minimum recommended vacuum level (microns) before closing service valves and charging a residential AC system?

    Answer: 500 microns

    Most manufacturers and industry standards require a vacuum of 500 microns or lower to ensure all moisture and non-condensables are removed.

  2. When installing a split-system AC, the indoor air handler should be level or slightly tilted in which direction?

    Answer: Tilted slightly toward the drain outlet

    The air handler should pitch slightly toward the condensate drain outlet so gravity assists condensate removal and prevents pan overflow.

  3. Which tool is used to flare the end of copper tubing for refrigerant line connections?

    Answer: Flaring tool

    A flaring tool is used to create a conical flare on the end of copper tubing that mates with flare fittings for leak-free refrigerant connections.

  4. What is the purpose of installing a P-trap on a condensate drain line?

    Answer: To prevent sewer gases from entering the unit

    A P-trap creates a water seal that prevents sewer gases and odors from being drawn into the air handler through the drain line.

  5. During a standing vacuum test, if micron gauge readings rise rapidly after the pump is isolated, this most likely indicates:

    Answer: A leak in the system or connections

    Rapid micron rise after pump isolation indicates a leak allowing air or moisture to enter the evacuated system.

  6. What is the correct sequence for connecting refrigerant manifold gauges to a system?

    Answer: Low-side blue hose to suction, high-side red hose to liquid/discharge, center yellow hose to refrigerant source

    Standard manifold gauge protocol connects blue (low) to suction service port, red (high) to liquid/discharge port, and yellow center hose to refrigerant cylinder or vacuum pump.

  7. When running refrigerant line sets through walls or floors, technicians must use:

    Answer: Grommets or bushings to protect tubing from abrasion

    Grommets or bushings protect copper refrigerant tubing from abrasion at wall penetrations, preventing wear-through that could cause leaks.

  8. What happens if a technician charges an AC system with non-condensable gases (such as air) still present?

    Answer: High-side pressure will be abnormally elevated

    Non-condensable gases raise head pressure above normal because they occupy condenser volume without condensing, reducing system efficiency and capacity.

  9. The recommended maximum lineset length without adding extra refrigerant charge for most mini-split systems is typically:

    Answer: 25 feet (pre-charged factory amount)

    Most mini-split systems are pre-charged at the factory for approximately 25 feet of lineset; additional refrigerant must be added for longer runs per manufacturer specs.

  10. Which type of copper tubing is required for ACR (Air Conditioning and Refrigeration) refrigerant line sets?

    Answer: Dehydrated, nitrogen-charged ACR copper tubing

    ACR-grade copper tubing is cleaned, dehydrated, and sealed with nitrogen to prevent moisture and contamination that would damage refrigerant systems.

  11. When insulating suction line tubing on an AC installation, the insulation must be:

    Answer: Continuous with no gaps, joints sealed, and of adequate wall thickness

    Suction line insulation must be continuous and fully sealed to prevent condensation, heat gain, and capacity loss throughout the entire lineset run.

  12. What is the primary reason technicians perform a nitrogen pressure test before evacuating a new AC system?

    Answer: To identify and locate leaks before pulling a vacuum

    Nitrogen pressure testing at 150–300 psig reveals leaks at joints and connections before the vacuum process, since a vacuum cannot identify leak locations.

  13. An outdoor condensing unit must be installed at least how far from the structure to ensure adequate airflow?

    Answer: Per manufacturer specifications, typically 12–18 inches minimum clearance

    Manufacturers specify minimum clearances (commonly 12–18 inches on sides) to ensure adequate airflow and prevent hot discharge air recirculation.

  14. When brazing copper refrigerant lines, nitrogen should be flowing through the tubing during the brazing process to:

    Answer: Prevent oxidation (scaling) inside the copper tubing

    Flowing dry nitrogen through copper tubing during brazing displaces oxygen, preventing copper oxide scale formation that could contaminate the refrigerant system.

  15. A dual-stage vacuum pump should have its oil changed:

    Answer: After each use or when the oil appears dark and contaminated

    Vacuum pump oil absorbs moisture during system evacuation and should be changed after every use to maintain the pump's ability to achieve deep vacuums.

  16. What is the correct refrigerant line sizing rule regarding the suction line versus the liquid line?

    Answer: The suction line is always larger in diameter than the liquid line

    Suction line carries low-pressure vapor (low density) and must be larger diameter than the liquid line to maintain proper refrigerant velocity and oil return.

  17. When an AC outdoor unit is installed on a rooftop, the mounting platform must:

    Answer: Be structurally rated for the unit weight and allow for vibration isolation

    Rooftop installations require structurally adequate, properly rated supports with vibration isolation pads to protect both the unit and the roof structure.

  18. Which EPA regulation governs the handling and recovery of refrigerants during AC service and installation?

    Answer: Section 608 of the Clean Air Act

    EPA Section 608 prohibits venting refrigerants and requires certified technicians to use approved recovery equipment during service, maintenance, and installation.

  19. What is 'triple evacuation' (also called 'three-step evacuation') used for?

    Answer: Removing moisture more effectively by breaking vacuum with dry nitrogen between pulls

    Triple evacuation involves pulling vacuum, breaking with dry nitrogen, then repeating twice more — each cycle draws out more moisture than a single long pull.

  20. The condensate drain line for a horizontal air handler installed in an attic should include:

    Answer: A secondary drain pan with a separate overflow drain or safety switch

    Attic-installed air handlers require a secondary condensate pan with drain or float switch to prevent ceiling water damage if the primary drain clogs.