  1. A contactor's coil is rated at 24V but the unit reads only 18V at the coil terminals during a call for cooling. What is the most likely cause?

    Answer: Low voltage from the transformer secondary

    Insufficient transformer output or excessive voltage drop in the 24V control circuit causes low coil voltage, preventing the contactor from pulling in fully.

  2. What is the purpose of a run capacitor in a single-phase PSC compressor motor?

    Answer: To maintain a phase shift that improves running efficiency

    A run capacitor stays in the circuit continuously, maintaining the phase shift between run and start windings to improve motor efficiency and power factor.

  3. A dual-run capacitor is labeled 40/5 MFD 440V. Which terminal pair connects to the compressor?

    Answer: HERM and C

    The HERM (hermetic) terminal and C (common) terminal form the 40 MFD section used for the compressor motor.

  4. Which safety device opens on a rise in discharge pressure and automatically resets when pressure drops?

    Answer: High-pressure switch (auto-reset)

    An auto-reset high-pressure switch opens the control circuit when discharge pressure exceeds its setpoint and closes again once pressure falls below the reset point.

  5. A technician measures 240V across a contactor's load-side terminals with the contactor pulled in. What does this indicate?

    Answer: Open contacts with load disconnected

    Voltage across open load-side terminals indicates the contactor is not closing; if the contacts were closed, voltage would be near zero across them.

  6. What happens to a start capacitor if it remains in the circuit longer than a few seconds?

    Answer: It overheats and can fail or explode

    Start capacitors are designed for short-duration use only; prolonged energization causes excessive heat buildup leading to failure.

  7. A potential relay used in a hard-start kit opens its contacts when which condition is met?

    Answer: Back-EMF across the start winding reaches approximately 75% of line voltage

    The potential relay monitors the voltage induced in the start winding; once back-EMF rises to the relay's pick-up voltage, it opens to remove the start capacitor from the circuit.

  8. What is the primary function of a crankcase heater on a compressor?

    Answer: To prevent refrigerant migration and oil dilution during the off cycle

    Crankcase heaters keep the compressor oil warm so refrigerant does not migrate into the crankcase and dilute the lubricant during shutdown.

  9. A time-delay relay in an AC control circuit is set for 5 minutes. What is its purpose?

    Answer: To prevent short-cycle compressor restarts

    Time-delay relays prevent short cycling by enforcing a minimum off time before the compressor can restart, protecting it from pressure equalization issues.

  10. When testing a capacitor with a capacitance meter, a reading of zero indicates what condition?

    Answer: The capacitor is open (internally broken)

    A zero capacitance reading means the internal element is open and the capacitor cannot store a charge.

  11. A compressor is wired to a 208/230V disconnect. Which wire gauge is required for a 30-amp circuit per NEC?

    Answer: 10 AWG

    NEC requires 10 AWG copper conductors for a 30-amp circuit at standard ambient temperatures.

  12. What type of transformer is typically used to supply 24V control voltage in a residential split system?

    Answer: Step-down transformer

    A step-down transformer reduces line voltage (120V or 240V primary) to 24V AC for the low-voltage control circuit.

  13. A technician finds a blown 3-amp control fuse repeatedly. What is the correct diagnostic approach?

    Answer: Disconnect control wiring sections to isolate the short before replacing the fuse

    Isolating sections of the control circuit identifies the shorted wire or component causing the overcurrent before replacing the fuse.

  14. What does a locked-rotor amperage (LRA) rating indicate on a compressor nameplate?

    Answer: The inrush current drawn when the motor first starts

    LRA is the high initial current drawn by a stalled or starting motor before it reaches operating speed.

  15. A variable-speed ECM blower motor is not responding to a speed signal from the control board. After confirming 24V supply to the module, what is the next step?

    Answer: Check the PWM or DC analog signal wire from the board to the motor module

    ECM motors receive a speed-control signal (PWM or 0–10V DC) from the board; loss of this signal causes the motor to default to a fixed speed or stop.

  16. What is the correct procedure for discharging a capacitor before handling it?

    Answer: Use a 10,000-ohm, 10-watt resistor across the terminals

    A resistor safely dissipates the stored charge without the arc that a direct short causes, which can damage terminals and capacitor internals.

  17. Which component in a gas furnace/AC system directly controls when the indoor blower comes on after heating ignition?

    Answer: Fan limit switch or control board fan delay

    A fan limit switch or control board fan-delay timer delays blower startup until the heat exchanger warms up, preventing cold air distribution.

  18. If a compressor's internal overload protects it from overheating but the unit starts immediately after being reset manually, what concern exists?

    Answer: The underlying cause of overheating was not corrected and the compressor will trip again

    Resetting an overload without diagnosing and correcting the root cause (e.g., low refrigerant, dirty coils, high ambient) will result in repeated tripping.

  19. What is the purpose of the C (common) terminal on a 24V thermostat circuit?

    Answer: It provides the return path for 24V AC from the transformer secondary

    The C wire completes the 24V control circuit by returning current to the transformer's secondary common, allowing smart thermostats and other loads to operate continuously.

  20. A technician reads 5 ohms between the compressor's common and run terminals and OL between common and start. What does this indicate?

    Answer: The start winding is open

    OL (overload/no continuity) between common and start indicates an open start winding, meaning the compressor motor needs replacement.