Services, Feeders, Branch Circuits Flashcards
6 cards from real TN LLE practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 6 Services, Feeders, Branch Circuits flashcards as text
An overhead service drop, with a voltage not exceeding 300V between conductors, passes over a residential roof with a 3-in-12 pitch. According to NEC 230.24(A), what is the minimum vertical clearance that must be maintained above the roof surface?
Answer: 8 feet
NEC 230.24(A) generally requires an 8-foot vertical clearance over roofs. An exception exists for roofs with a slope of 4 in 12 or greater, which allows a reduction to 3 feet. Since the roof pitch is 3-in-12 (less than 4-in-12), the general requirement of 8 feet applies.
An electrician is installing a 120/240V multiwire branch circuit to supply two separate kitchen countertop receptacle circuits. Which of the following is an NEC requirement for this type of circuit?
Answer: A means must be provided to simultaneously disconnect all ungrounded conductors.
NEC 210.4(B) requires that for multiwire branch circuits, a means must be provided to simultaneously disconnect all ungrounded conductors where the circuit originates. This is typically accomplished with a two-pole circuit breaker or two single-pole breakers with an approved handle tie.
What is the minimum feeder conductor ampacity required for a load consisting of a 40-amp continuous load and a 30-amp noncontinuous load?
Answer: 80 amps
According to NEC 215.2(A)(1), the feeder ampacity must be not less than the noncontinuous load plus 125% of the continuous load. Calculation: (1.25 x 40A) + 30A = 50A + 30A = 80A.
According to NEC 230.70(A)(1), where must the service disconnecting means for a one-family dwelling be located?
Answer: At a readily accessible location either outside or inside nearest the point of conductor entrance.
NEC 230.70(A)(1) mandates that the service disconnect be installed in a readily accessible location. This can be on the exterior of the building or just inside, nearest the point where the service conductors enter, to limit the amount of unprotected service conductor inside the structure.
When calculating the load for a branch circuit supplying a fixed multioutlet assembly (e.g., plugmold) in a commercial building where appliances are not likely to be used simultaneously, what is the standard load allowance per section?
Answer: 180 VA for every 5-foot section or fraction thereof
NEC 220.14(H)(1) specifies that for a fixed multioutlet assembly where simultaneous use is unlikely, each 5-foot section (or any fraction of a 5-foot section) is calculated at 180 volt-amperes.
A main-lug-only (MLO) panelboard is installed as a subpanel in a workshop. According to NEC 408.36, which of the following is required?
Answer: It must be protected by an overcurrent device on its supply side.
NEC 408.36 requires that each panelboard be protected by an overcurrent protective device (OCPD). For a main-lug-only panel, this OCPD must be located on the supply side of the panelboard, typically the breaker in the main panel that feeds the subpanel.
How this page was made: written with AI tools and published by Nathan Beja, founder of Practice Test Geeks, who is responsible for its content. Exam facts are checked against the official sources listed below. Not reviewed by a subject-matter expert. Editorial policy
Sources & references
Exam facts on this page (fees, format, dates, passing scores) are checked against these official sources; the date is our last check. Editorial policy
- tn.gov — Score validity, exam information · verified Oct 2026
- test-takers.psiexams.com — Exam information · verified Nov 2026
- tnboi.provexam.com — Test delivery, fees, exam format, passing score, retake fee, retake policy, score release, time limit, exam information · verified Oct 2026