← All TN LLE Flashcard Decks

Motors and Motor Circuits Flashcards

6 cards from real TN LLE practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 6 Motors and Motor Circuits flashcards as text
  1. What is the minimum ampacity required for the branch-circuit conductors supplying a 10 HP, 230-volt, 3-phase squirrel-cage motor?

    Answer: 35A

    First, find the motor's Full-Load Current (FLC) from NEC Table 430.250, which is 28A. NEC 430.22 requires branch-circuit conductors to have an ampacity of at least 125% of the motor FLC. The calculation is 28A x 1.25 = 35A.

  2. What is the maximum standard size inverse-time circuit breaker that can be used for branch-circuit, short-circuit, and ground-fault protection for a 10 HP, 230V, 3-phase motor (FLC 28A)?

    Answer: 70A

    NEC Table 430.52 specifies the maximum rating of a motor branch-circuit protective device. For a polyphase squirrel-cage motor and an inverse-time breaker, the maximum is 250% of the FLC. The calculation is 28A x 2.50 = 70A. Since 70A is a standard size per 240.6(A), this is the maximum size permitted.

  3. A feeder supplies two 3-phase, 230V motors: a 10 HP (FLC 28A) and a 5 HP (FLC 15.2A). What is the minimum required ampacity for the feeder conductors?

    Answer: 50.2A

    Per NEC 430.24, the feeder ampacity must be at least 125% of the largest motor's FLC plus the sum of the FLCs of the other motors. The calculation is (28A x 1.25) + 15.2A = 35A + 15.2A = 50.2A. The conductors must have an ampacity of at least 50.2A.

  4. Using the same motors from the previous question (10 HP and 5 HP), what is the maximum standard size inverse-time circuit breaker permitted for the feeder protection?

    Answer: 80A

    NEC 430.62(A) states the feeder protective device rating shall not be greater than the largest branch-circuit protective device plus the FLC of the other motors. The largest branch device (for the 10 HP motor) is 70A (28A x 250%). The calculation is 70A + 15.2A = 85.2A. Since this is not a standard size, you must round down to the next standard size, which is 80A.

  5. What is the maximum setting for a separate overload protection device for a continuous-duty motor with a nameplate FLC of 40A, a service factor of 1.15, and a temperature rise of 40°C?

    Answer: 50A

    According to NEC 430.32(A)(1), for a motor with a marked service factor of 1.15 or greater or a marked temperature rise of 40°C or less, the overload device shall be selected at not more than 125% of the motor nameplate FLC. The maximum setting is 40A x 1.25 = 50A.

  6. A motor control circuit is tapped from the load side of a 60A branch-circuit breaker and the conductors do not leave the enclosure. What is the minimum size copper conductor required for this control circuit?

    Answer: 14 AWG

    NEC 430.72(B) and Table 430.72(B) provide the requirements for motor control circuit conductor protection. Since the conductors do not extend beyond the enclosure, Column B applies. For a protective device rated at 60A, the minimum control circuit conductor size is 14 AWG copper.

How this page was made: written with AI tools and published by Nathan Beja, founder of Practice Test Geeks, who is responsible for its content. Exam facts are checked against the official sources listed below. Not reviewed by a subject-matter expert. Editorial policy

Sources & references

Exam facts on this page (fees, format, dates, passing scores) are checked against these official sources; the date is our last check. Editorial policy

  1. tn.gov — Score validity, exam information · verified Oct 2026
  2. test-takers.psiexams.com — Exam information · verified Nov 2026
  3. tnboi.provexam.com — Test delivery, fees, exam format, passing score, retake fee, retake policy, score release, time limit, exam information · verified Oct 2026