  1. A hermetic refrigerant motor-compressor has a rated-load current (RLC) of 20A. What is the minimum ampacity for the branch-circuit conductors supplying this motor-compressor?

    Answer: 25A

    NEC 440.32 requires branch-circuit conductors supplying a single motor-compressor to have an ampacity of not less than 125% of the motor-compressor's rated-load current. Therefore, 20A multiplied by 1.25 equals 25A.

  2. According to NEC Article 440, a disconnecting means for an air-conditioning unit must be located within sight from the unit. What is the maximum distance to be considered "within sight"?

    Answer: 50 feet

    The term "In Sight From" is defined in NEC Article 100 as being visible and not more than 50 feet distant from the other. This rule ensures a technician can safely de-energize the unit while working on it.

  3. An A/C unit's nameplate lists the rated-load current as 24A and specifies a "Maximum Fuse Size" of 40A. What is the maximum size inverse-time circuit breaker that can be used for branch-circuit protection?

    Answer: 40A

    NEC 440.4(B) states that equipment shall be installed in accordance with the manufacturer's recommendations included in the listing or labeling. If the nameplate specifies a maximum fuse or HACR circuit breaker size, that value must not be exceeded.

  4. A 120-volt, cord-and-plug-connected room air conditioner is installed on a branch circuit that also supplies lighting outlets. What is the maximum permissible rated current of the air conditioner?

    Answer: 50% of the branch-circuit rating

    According to NEC 440.62(C), where a cord-and-plug-connected room air conditioner is connected to a branch circuit that also supplies lighting units or other appliances, the total rated current of the air conditioner shall not exceed 50% of the branch-circuit rating.

  5. Which of the following is NOT a required marking on an air-conditioning unit's nameplate according to NEC 440.4?

    Answer: Recommended conductor size

    NEC 440.4(A) lists required markings, including rated-load current, voltage, phase, and manufacturer's name. It does not mandate the recommended conductor size, as the electrician is responsible for calculating this based on the NEC.

  6. An air-conditioning unit has a rated-load current of 18A and a locked-rotor current of 90A. What is the minimum ampere rating for the required disconnecting means?

    Answer: 30A

    As per NEC 440.12(A)(1), the disconnecting means must have an ampere rating of at least 115% of the motor-compressor's rated-load current. In this case, 18A * 1.15 = 20.7A. A standard 30A non-fused disconnect is the minimum standard size that meets this requirement.

How this page was made: written with AI tools and published by Nathan Beja, founder of Practice Test Geeks, who is responsible for its content. Exam facts are checked against the official sources listed below. Not reviewed by a subject-matter expert. Editorial policy

Sources & references

Exam facts on this page (fees, format, dates, passing scores) are checked against these official sources; the date is our last check. Editorial policy

  1. tn.gov — Score validity, exam information · verified Oct 2026
  2. test-takers.psiexams.com — Exam information · verified Nov 2026
  3. tnboi.provexam.com — Test delivery, fees, exam format, passing score, retake fee, retake policy, score release, time limit, exam information · verified Oct 2026