Fault Current & OCPD Ratings Flashcards
6 cards from real TN LLE practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 6 Fault Current & OCPD Ratings flashcards as text
The marking 'AIC' on a circuit breaker or fuse stands for:
Answer: Ampere Interrupting Capacity
AIC stands for Ampere Interrupting Capacity, also known as the Interrupting Rating (IR). This rating indicates the maximum amount of fault current that the overcurrent protective device (OCPD) can safely interrupt without failing or causing a hazard.
According to NEC 110.9, an overcurrent protective device's interrupting rating must be:
Answer: Equal to or greater than the available fault current.
NEC 110.9 is a fundamental safety rule stating that equipment intended to interrupt current at fault levels must have an interrupting rating sufficient for the current that is available at the line terminals of the equipment. This means the device's rating must be equal to or greater than the available fault current.
Which of the following actions would most likely INCREASE the available fault current at a panelboard?
Answer: Replacing the upstream transformer with a larger kVA unit
The size of the upstream transformer is a primary factor in determining available fault current; a larger kVA transformer has a lower internal impedance and can deliver more current during a fault. Longer or smaller conductors would add impedance and decrease fault current.
A panelboard is marked "Suitable for use as service equipment only when not more than six main circuit breakers are installed." This is an example of what NEC rule?
Answer: The Six Disconnect Rule (230.71)
This marking relates directly to NEC 230.71, which permits up to six switches or circuit breakers to serve as the service disconnecting means. The panelboard's listing and marking ensure it is used in compliance with this 'six-handle rule' for service equipment.
What is required for a 'series rated' overcurrent protection system to be compliant with the NEC?
Answer: The combination must be specifically tested and listed for series use.
NEC 240.86 allows for series ratings where a line-side device (like a main breaker) with a high AIC rating can protect a load-side device (like a branch breaker) with a lower AIC rating. For this to be compliant, the combination of devices must be specifically tested and listed by the manufacturer for that purpose.
The general rule in NEC 240.21 requires that overcurrent protection for a conductor be located:
Answer: At the point where the conductor receives its supply.
NEC 240.21(A) establishes the fundamental rule for overcurrent protection. It states that protection shall be provided in each ungrounded conductor at the point where the conductors receive their supply, preventing the entire length of the conductor from being overloaded.
How this page was made: written with AI tools and published by Nathan Beja, founder of Practice Test Geeks, who is responsible for its content. Exam facts are checked against the official sources listed below. Not reviewed by a subject-matter expert. Editorial policy
Sources & references
Exam facts on this page (fees, format, dates, passing scores) are checked against these official sources; the date is our last check. Editorial policy
- tn.gov — Score validity, exam information · verified Oct 2026
- test-takers.psiexams.com — Exam information · verified Nov 2026
- tnboi.provexam.com — Test delivery, fees, exam format, passing score, retake fee, retake policy, score release, time limit, exam information · verified Oct 2026