← All TN LLE Flashcard Decks

Commercial Load Calculations Flashcards

6 cards from real TN LLE practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 6 Commercial Load Calculations flashcards as text
  1. What is the calculated general lighting load for a 20,000 sq. ft. office building after applying all applicable demand factors?

    Answer: 41,250 VA

    First, calculate the total lighting VA: 20,000 sq. ft. x 3.5 VA/sq. ft. (Table 220.12) = 70,000 VA. Then, apply demand factors from Table 220.42: the first 12,500 VA is at 100%, and the remainder (57,500 VA) is at 50%. The final calculated load is 12,500 VA + (57,500 VA x 0.50) = 41,250 VA.

  2. A commercial occupancy has 100 general-purpose duplex receptacles. What is the calculated load for these receptacles after applying demand factors?

    Answer: 14,000 VA

    Per NEC 220.14(I), each receptacle outlet is calculated at 180 VA. The total connected load is 100 outlets x 180 VA = 18,000 VA. According to NEC 220.44, the first 10 kVA (10,000 VA) is taken at 100%, and the remainder (8,000 VA) is at 50%. The calculated load is 10,000 VA + (8,000 VA x 0.50) = 14,000 VA.

  3. What is the calculated load for 40 linear feet of show-window lighting in a retail store?

    Answer: 8,000 VA

    NEC 220.14(G) requires that show-window lighting be calculated at a minimum of 200 VA per linear foot. Therefore, the total calculated load is 40 ft x 200 VA/ft = 8,000 VA. This load is added to the general lighting load before general lighting demand factors are applied.

  4. A commercial kitchen contains 5 pieces of permanently installed cooking equipment with a total nameplate rating of 60 kW. What is the calculated demand load for this equipment?

    Answer: 42 kW

    NEC 220.56 and the associated Table 220.56 allow for a demand factor to be applied to commercial kitchen equipment. For 5 appliances, the demand factor is 70%. The calculated load is 60 kW x 0.70 = 42 kW.

  5. A 4-wire, 3-phase, 208Y/120V system serves a non-linear load with a calculated maximum unbalanced current of 250A. What is the calculated demand load on the neutral conductor?

    Answer: 235A

    According to NEC 220.61(C), a demand factor of 70% can be applied to the portion of the unbalanced load exceeding 200A. The first 200A is calculated at 100%. The calculation is: 200A + ((250A - 200A) x 0.70) = 200A + (50A x 0.70) = 200A + 35A = 235A.

  6. What is the feeder demand load for fixed electric space heating in a commercial building with three units rated at 5 kW, 6 kW, and 10 kW?

    Answer: 21 kW

    According to NEC 220.51, the load for fixed electric space heating is calculated at 100% of the total connected load. There are no demand factors for commercial space heating unless specific conditions for diversity are met, which are not mentioned here. The total load is 5 kW + 6 kW + 10 kW = 21 kW.

How this page was made: written with AI tools and published by Nathan Beja, founder of Practice Test Geeks, who is responsible for its content. Exam facts are checked against the official sources listed below. Not reviewed by a subject-matter expert. Editorial policy

Sources & references

Exam facts on this page (fees, format, dates, passing scores) are checked against these official sources; the date is our last check. Editorial policy

  1. tn.gov — Score validity, exam information · verified Oct 2026
  2. test-takers.psiexams.com — Exam information · verified Nov 2026
  3. tnboi.provexam.com — Test delivery, fees, exam format, passing score, retake fee, retake policy, score release, time limit, exam information · verified Oct 2026