How does 3-wire control of a VFD differ from 2-wire control?
Answer: 3-wire uses momentary start and stop pushbuttons with a seal-in function
3-wire control latches a run from a momentary start and drops out on a momentary stop, while 2-wire uses one maintained contact.
A VFD's 4-20 mA speed input is scaled 0-60 Hz. What output frequency does a 12 mA signal command?
Answer: 30 Hz
12 mA is 50% of the 16 mA span (8/16), so the output is 50% of 60 Hz, or 30 Hz.
Why should a VFD usually not be started and stopped by cycling its input contactor many times an hour?
Answer: Repeated power-ups stress the DC bus precharge circuit and capacitors
Each power-up sends inrush through the precharge circuit, so frequent cycling shortens drive life; use the run/stop inputs instead.
After a VFD is installed, the motor turns in the wrong direction. Which correction is acceptable?
Answer: Swap two output motor leads or change the direction parameter
Output phase sequence sets rotation, so swapping two motor leads or using the drive's direction setting reverses it; swapping input leads has no effect.
A VFD trips on 'ground fault' as soon as it starts. What should a technician check first?
Answer: The motor and output cable insulation to ground
A ground fault means current is leaking to earth, most often through damaged motor windings or cable insulation, which an insulation test can find.
How is shielded VFD motor cable normally terminated to reduce electrical noise?
Answer: Shield bonded to ground at both the drive and motor ends
Bonding the power-cable shield at both ends gives high-frequency common-mode currents a low-impedance return path, which cuts EMI.
A centrifugal fan on a VFD is slowed to 80% speed. About what percent of full-speed power does it need?
Answer: 51%
By the affinity laws, power varies with the cube of speed: 0.8³ ≈ 0.51.