About what DC bus voltage would you measure on a VFD fed from 480 VAC three-phase with no load?
Answer: 650 VDC
A rectified three-phase bus sits near 1.35 × line voltage, which is about 650 VDC for 480 VAC.
A VFD trips on DC bus overvoltage every time a high-inertia load decelerates. Which fix is most appropriate?
Answer: Lengthen the deceleration time or add a braking resistor
Regenerated energy raises the bus voltage, so a slower decel or dissipating that energy through a braking resistor prevents the trip.
In a VFD with dynamic braking, how is the braking resistor connected?
Answer: Across the DC bus through a brake chopper transistor
The brake chopper switches the resistor across the DC bus when bus voltage passes a threshold, turning excess energy into heat.
Which semiconductor devices are most often used to switch the inverter output section of a modern low-voltage VFD?
Answer: IGBTs
IGBTs combine fast switching with high current capacity, which makes them the standard for PWM inverter output.
After disconnecting power from a VFD, why must a technician wait and verify voltage before touching internal components?
Answer: The DC bus capacitors can hold a dangerous charge
Bus capacitors can stay charged to hundreds of volts for several minutes, so the bus must be measured before work begins.
What is the main purpose of installing a line (input) reactor ahead of a VFD?
Answer: To reduce input harmonics and protect the drive from line transients
A line reactor adds impedance that smooths current draw, lowers harmonics, and limits surge currents from the supply.
A VFD feeds a motor through a very long cable run, and motor insulation is failing early. What is the likely cause?
Answer: Reflected-wave voltage spikes at the motor terminals
Fast PWM edges reflect along long leads and can nearly double the peak voltage at the motor, which stresses insulation; dV/dt filters or load reactors reduce this.