Electrical Control Systems Flashcards

6 cards from real SACA practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 6 Electrical Control Systems flashcards as text
  1. What is 'power factor' in AC electrical systems and why is low power factor a problem in industrial facilities?

    Answer: Power factor is the ratio of real power to apparent power; low power factor means more current is drawn for the same useful work, increasing distribution losses and utility demand charges

    Power factor (PF = kW/kVA) represents how effectively current is converted to useful work. Inductive loads (motors, transformers) draw reactive current that doesn't do work but still flows through cables — increasing losses and utility demand charges.

  2. What is the purpose of a 'ground fault circuit interrupter' (GFCI) in industrial electrical systems?

    Answer: To detect small leakage currents flowing to ground and quickly disconnect power to prevent electrocution

    A GFCI monitors the difference between supply and return current (typically using a toroidal current transformer). If more than ~5mA flows to ground (indicating current through a person), it trips within 25ms — before the current level causes ventricular fibrillation.

  3. In industrial panel wiring, what is the standard color convention for DC control wiring in North America?

    Answer: Red = positive (+), Black = negative (−), Green = ground

    North American DC wiring convention per NEC/NFPA79: Red = positive DC, Black = negative DC (or sometimes Blue in some standards), Green or Green/Yellow = protective earth ground.

  4. What is the function of an 'autotransformer' starter for large induction motors?

    Answer: It uses transformer taps to apply a fraction of line voltage during starting, then switches to full voltage at running speed

    An autotransformer starter applies reduced voltage (via 50%, 65%, or 80% taps) to the motor during starting, limiting inrush current. Once the motor reaches near-synchronous speed, it switches to full line voltage — producing higher starting torque than star-delta for the same current.

  5. What is 'arc flash' hazard in electrical switchgear, and what does an 'arc flash study' determine?

    Answer: The explosive release of energy from an electrical arc fault, causing burns and blast injury; the study determines the incident energy and required PPE category for each panel

    Arc flash occurs when a fault creates a plasma arc that releases enormous thermal energy (thousands of degrees Celsius) in milliseconds, causing severe burns, blast injury, and fires. An arc flash study calculates incident energy (cal/cm²) at each panel to specify required flame-resistant PPE.

  6. What does 'lockout/tagout' (LOTO) procedure require before performing electrical maintenance on industrial control panels?

    Answer: Isolating all energy sources, applying lockout devices, and verifying the equipment is de-energized before any maintenance work

    LOTO (OSHA 29 CFR 1910.147) requires: identifying all energy sources, turning off/disconnecting each source, applying a personal lockout device (padlock), releasing stored energy (capacitors, springs, gravity), then verifying zero energy state with a meter before work begins.