  1. An infrared scan of an electrical panel shows one breaker lug much hotter than its neighbors under similar load. What is the most likely cause?

    Answer: A loose or high-resistance connection

    Loose or corroded connections increase resistance, which causes I²R heating that thermography detects.

  2. When using an IR camera on a shiny, polished metal surface, what error is most likely if emissivity is not corrected?

    Answer: The reading will be falsely low

    Low-emissivity shiny surfaces emit little infrared energy and reflect surroundings, so uncorrected readings are usually too low.

  3. Airborne ultrasound instruments used for compressed air leak detection commonly operate near which frequency?

    Answer: 40 kHz

    Turbulent gas leaks generate strong ultrasound around 38-40 kHz, which handheld detectors convert to audible sound.

  4. An oil analysis report shows a sharp rise in silicon content. What does this most often indicate?

    Answer: Dirt or dust contamination entering the system

    Silicon is a primary element in airborne dirt and sand, so a rise usually signals failed seals or breathers.

  5. Which oil analysis technique examines the shape, size, and type of wear particles to identify the wear mechanism?

    Answer: Analytical ferrography

    Ferrography separates wear particles magnetically for microscopic examination of their morphology, revealing cutting, fatigue, or sliding wear.

  6. An ISO 4406 fluid cleanliness code such as 18/16/13 reports particle counts at which size thresholds?

    Answer: 4, 6, and 14 microns

    ISO 4406 uses three range numbers for particles greater than 4, 6, and 14 microns per milliliter.

  7. Which laboratory test is most accurate for measuring low levels of water contamination in lubricating oil?

    Answer: Karl Fischer titration

    Karl Fischer titration chemically reacts with water to quantify it accurately down to parts-per-million levels.

Written and edited by , founder of Practice Test Geeks, with AI assistance. Exam facts are checked against the official sources linked below. Editorial policy

Sources & references

Exam facts on this page (fees, format, dates, passing scores) are checked against these official sources; the date is our last check. Editorial policy

  1. saca.org — Retake policy, score release, test delivery, eligibility · verified Nov 2026