  1. A hermetic compressor motor draws locked-rotor amperage (LRA) of 45A. What is the minimum wire gauge required for a 240V single-phase circuit using copper conductors at 75°C?

    Answer: 10 AWG

    LRA × 1.25 = 56.25A; 10 AWG copper at 75°C is rated for 35A continuous, but NEC 440.52 sizing for motors requires selecting wire rated for at least 125% of FLA, and 10 AWG handles the circuit with proper OCPD.

  2. Which type of overload relay automatically resets after cooling down without requiring manual intervention?

    Answer: Auto-reset bimetallic relay

    An auto-reset bimetallic overload relay restores the circuit automatically once the bimetal strip cools and returns to its original position.

  3. A capacitor-start, capacitor-run (CSCR) motor fails to start but hums loudly. Which component is most likely faulty?

    Answer: Start capacitor or centrifugal switch

    Humming without starting indicates the start winding circuit is open, typically caused by a failed start capacitor or a defective centrifugal switch that won't close.

  4. What does a megohmmeter (megger) primarily measure in refrigeration system electrical diagnostics?

    Answer: Insulation resistance of motor windings

    A megohmmeter applies high DC voltage (typically 500–1000V) to measure insulation resistance in megohms, revealing winding degradation or moisture ingress.

  5. In a refrigeration control circuit, a normally open (NO) pressure switch closes at 250 psig and opens at 300 psig. This switch is functioning as a:

    Answer: High-pressure operating control

    A switch that closes on pressure rise and opens at a high setpoint is a high-pressure operating control, cycling the system to maintain discharge pressure within a range.

  6. A three-phase compressor motor is running but drawing unequal current on the three legs. The most likely cause is:

    Answer: Voltage imbalance or open motor winding

    Current imbalance in a three-phase motor typically indicates either a supply voltage imbalance or a partially shorted/open winding, both of which cause unequal current draw per phase.

  7. Which NEC article specifically governs the installation of air-conditioning and refrigerating equipment?

    Answer: Article 440

    NEC Article 440 covers air-conditioning and refrigerating equipment, including hermetic refrigerant motor-compressors and their associated electrical circuits.

How this page was made: written with AI tools and published by Nathan Beja, founder of Practice Test Geeks, who is responsible for its content. Exam facts are checked against the official sources listed below. Not reviewed by a subject-matter expert. Editorial policy

Sources & references

Exam facts on this page (fees, format, dates, passing scores) are checked against these official sources; the date is our last check. Editorial policy

  1. cdn.ymaws.com — Test delivery, retake fee, score release, time limit · verified Oct 2026
  2. rses.org — Eligibility, fees, exam format, passing score, retake policy · verified Oct 2026