← All RCDD Flashcard Decks

Cabling Infrastructure and Pathways Flashcards

6 cards from real RCDD practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 6 Cabling Infrastructure and Pathways flashcards as text
  1. What is the recommended minimum inside diameter for a single-user conduit stub-up at a workstation outlet?

    Answer: 25 mm (1 in)

    ANSI/TIA-569 recommends a minimum 25 mm (1 inch) inside diameter for single-user outlet conduit stubs to accommodate telecommunications cabling.

  2. How should optical fiber cable be protected where it passes through a wall or floor?

    Answer: Installed in a sleeve or conduit

    Optical fiber cable must be installed in a sleeve or conduit wherever it passes through walls or floors to prevent physical damage and maintain fire ratings.

  3. What is the primary purpose of a cable runway (ladder rack) in a data center?

    Answer: To provide an overhead cable management pathway between equipment racks

    Cable runways (ladder racks) provide overhead pathways for routing and managing cables between equipment racks in data center environments.

  4. Per BICSI TDMM, what is the maximum span between cable tray support brackets for standard aluminum tray?

    Answer: 3 m (10 ft)

    Standard aluminum cable trays should have support brackets spaced no more than 3 meters (10 feet) apart to prevent deflection under cable load.

  5. Which of the following correctly describes a modular furniture system's telecommunications cabling path?

    Answer: Cables run within modular furniture raceways from a consolidation point or multi-user outlet

    Modular furniture cabling uses consolidation points or multi-user outlets (MUTOAs) in the open office, with cables routed within the furniture raceways to each workstation.

  6. What is the primary reason for derating cable ampacity when cables are bundled in a conduit?

    Answer: Heat buildup from multiple cables reduces individual cable current capacity

    Bundled cables generate cumulative heat that cannot dissipate as efficiently, requiring ampacity derating to prevent insulation damage and fire hazards.