What is the significance of duct pressure classification (e.g., 1/2", 1", 2", 3", 4", 6", 10" WG)?
Answer: It determines the construction standards including metal gauge, reinforcement spacing, and sealing requirements
Duct pressure class determines all construction requirements including minimum metal gauge, joint types, reinforcement methods and spacing, and sealing class. Higher pressures require heavier construction.
What is a 'mixed air plenum' in an air handling unit?
Answer: A chamber where return air and outdoor air are blended together before passing through filters and coils
The mixed air plenum is located upstream of the filters and coils where return air from the building is blended with fresh outdoor air. Dampers control the ratio of return to outdoor air.
What is the purpose of a 'flexible connector' between the air handling unit and the ductwork?
Answer: To isolate fan vibration from the duct system and accommodate thermal movement
Flexible connectors (typically fabric or rubber) isolate mechanical vibration from the AHU fans, preventing it from transmitting through the rigid ductwork. They also accommodate thermal expansion.
What duct material is required for a fume exhaust system handling corrosive chemicals?
Answer: Stainless steel, PVC, or fiberglass reinforced plastic depending on the chemical
Corrosive chemical fume exhaust requires materials resistant to the specific chemicals involved. Stainless steel, PVC, polypropylene, or fiberglass reinforced plastic are selected based on chemical compatibility.
What is the purpose of a 'test and balance' (TAB) procedure after duct installation?
Answer: To measure and adjust airflows, temperatures, and pressures throughout the system to ensure design conditions are met
Test and balance is a systematic procedure to measure actual airflows at all supply and return outlets, adjust dampers, and verify that the system delivers the designed air quantities, temperatures, and pressures.
What is the maximum permitted duct leakage rate for a SMACNA Seal Class A system at 2" WG?
Answer: Approximately 1% of system airflow or less, as specified by CL = 6 formula
SMACNA Seal Class A at 2" WG permits minimal leakage calculated by the formula CL x P^0.65 where CL=6 for Class A. This typically works out to approximately 1% or less of system airflow.
How this page was made: written with AI tools and published by Nathan Beja, founder of Practice Test Geeks, who is responsible for its content. Exam facts are checked against the official sources listed below. Not reviewed by a subject-matter expert. Editorial policy
Sources & references
Exam facts on this page (fees, format, dates, passing scores) are checked against these official sources; the date is our last check. Editorial policy
- skilledtradesontario.ca — Renewal, retake fee, score validity, test delivery, fees, retake policy, passing score, score release, time limit · verified Oct 2026
- red-seal.ca — Exam format · verified Oct 2026