Refrigerant Handling Flashcards
6 cards from real 313A practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 6 Refrigerant Handling flashcards as text
What is the purpose of evacuating a refrigeration system and what vacuum level should be achieved?
Answer: Evacuation removes air and moisture by pulling a deep vacuum; target is 500 microns (0.5 mm Hg) or lower for systems using hygroscopic refrigerants like R-410A
Evacuation uses a vacuum pump to remove non-condensable gases (air) and moisture from a refrigeration system. Air reduces efficiency and raises head pressure, while moisture causes acid formation, corrosion, and freeze-ups. A target of 500 microns or lower is standard for R-410A systems, held for at least 15-30 minutes to confirm a tight system.
What is the proper method for charging R-410A refrigerant into a system?
Answer: Charge as a liquid through the high side (liquid line) or through the suction side with a metering device to prevent liquid slugging, because R-410A is a near-azeotropic blend
R-410A is a near-azeotropic blend (R-32/R-125) that must be charged as a liquid to maintain the correct composition. Liquid can be charged through the liquid line directly or through the suction side using a restrictor to flash the liquid to vapour before it enters the compressor. The cylinder must be inverted or use a dip tube.
What is a triple evacuation and when is it recommended?
Answer: Three cycles of pulling a vacuum then breaking with dry nitrogen, followed by a final deep vacuum; recommended for systems with significant moisture contamination
A triple evacuation involves: (1) pulling a vacuum, (2) breaking the vacuum with dry nitrogen to atmospheric pressure, (3) repeating the vacuum and nitrogen break, and (4) pulling a final deep vacuum to 500 microns or below. The nitrogen sweeps help remove moisture more effectively than a single deep vacuum alone.
What are the dangers of mixing different refrigerants in a system?
Answer: It can create unpredictable pressures, reduce capacity, damage the compressor, void equipment warranties, and create unsafe operating conditions
Mixing refrigerants creates an unknown blend with unpredictable pressure-temperature characteristics, potentially causing dangerously high pressures, compressor damage from oil compatibility issues, reduced capacity, and voided warranties. Mixed refrigerants cannot be recycled or reclaimed and must be destroyed. This is why recovery cylinders are dedicated to specific refrigerants.
What is a standing pressure test and what does it verify?
Answer: Pressurizing the system with dry nitrogen to a specified pressure and monitoring for a drop over time to verify the system has no leaks
A standing pressure test involves pressurizing the system with dry nitrogen (often with a trace of refrigerant for electronic leak detection) to the test pressure specified by the equipment manufacturer. The system is then isolated and monitored for a minimum of 24 hours. Any pressure drop indicates a leak that must be found and repaired.
Under Canada's Environmental Protection Act, what is the maximum allowable leak rate for commercial refrigeration systems before repairs are required?
Answer: Systems containing more than a threshold amount of refrigerant must repair leaks within a specified timeframe, and annual leak rates exceeding approximately 10-20% (depending on province) require mandatory reporting and repair
Canadian federal and provincial regulations require operators of commercial and industrial refrigeration systems to track refrigerant usage, repair identified leaks promptly, and report systems exceeding allowable annual leak rates. Specific thresholds vary by province but generally range from 10% to 20% of total charge. Chronic leaking systems may face fines or mandatory replacement.
How this page was made: written with AI tools and published by Nathan Beja, founder of Practice Test Geeks, who is responsible for its content. Exam facts are checked against the official sources listed below. Not reviewed by a subject-matter expert. Editorial policy
Sources & references
Exam facts on this page (fees, format, dates, passing scores) are checked against these official sources; the date is our last check. Editorial policy
- skilledtradesontario.ca — Score validity, eligibility, retake policy, renewal, fees, test delivery, passing score, score release, time limit · verified Oct 2026
- red-seal.ca — Exam format · verified Oct 2026