PLC Safety & Functional Safety Flashcards

6 cards from real PLC practice questions. Tap to flip, then mark Knew It or Still Learning โ€” missed cards come back until you master them.

Read the first 6 PLC Safety & Functional Safety flashcards as text
  1. Which IEC standard covers functional safety of electrical, electronic, and programmable electronic safety-related systems?

    Answer: IEC 61508

    IEC 61508 is the umbrella standard for functional safety of E/E/PE (electrical, electronic, and programmable electronic) safety-related systems.

  2. What does 'de-energize to trip' mean in safety PLC output design?

    Answer: The safety output removes power to actuate the safe state, so a loss of power also triggers the safe state

    De-energize to trip means the output coil de-energizes to initiate the safe state, ensuring that a wiring or power failure also drives the system safe.

  3. What is the Safe Failure Fraction (SFF) used to determine?

    Answer: The proportion of failures that are either safe or detected dangerous failures within a safety component

    SFF represents the fraction of all failure modes that result in safe or detected dangerous states, used to determine the maximum achievable SIL for a component.

  4. In functional safety terminology, what is a 'proof test'?

    Answer: A periodic test of a safety function to detect dangerous undetected failures

    A proof test is a scheduled functional test of a safety instrumented function to reveal dangerous undetected failures and restore the system to its designed SIL.

  5. Which safety architecture uses two independent channels where both must detect a fault to initiate a trip (voting logic)?

    Answer: 2oo2 (two-out-of-two)

    A 2oo2 architecture requires both channels to agree that a fault exists before a trip is initiated, offering high availability but lower fault detection.

  6. What is the primary advantage of a 2oo3 voting architecture in safety PLCs?

    Answer: It balances fault tolerance and availability by allowing one channel failure without causing a spurious trip or missing a real fault

    A 2oo3 architecture tolerates one failed channel without a spurious trip while still detecting a real hazard when two of three channels agree.

PLC Safety & Functional Safety Flashcards โ€” PLC Study Cards with Answers