Oil Storage Tank Regulations Flashcards
6 cards from real OFTEC practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 6 Oil Storage Tank Regulations flashcards as text
What type of base is required for a plastic oil storage tank?
Answer: A level, non-combustible base extending 300mm beyond the tank on all sides
Plastic oil tanks require a firm, level, non-combustible base (typically a concrete slab) that extends at least 300mm beyond the tank footprint on all sides. This prevents settlement, provides stability, and offers fire protection from ground level.
What is an integrally bunded oil tank?
Answer: A tank with a built-in secondary containment wall forming a tank-within-a-tank
An integrally bunded tank has the secondary containment built into its construction — essentially a tank within a tank. This eliminates the need for a separate bund wall and is popular for domestic installations where space is limited.
What is the minimum distance an oil tank must be from a non-fire-rated building if a fire barrier wall is NOT installed?
Answer: 1.8 metres for a plastic tank
Without a fire barrier, a plastic oil tank must be at least 1.8 metres from a non-fire-rated building. Steel tanks require 1.0 metre. These distances can be reduced with an appropriate 30-minute fire-rated barrier wall.
What must be installed on the oil supply pipe where it passes through or under a building?
Answer: A fire valve externally and the pipe must be in a protective sleeve
Where an oil supply pipe enters or passes under a building, a fire valve must be installed on the external side. The pipe should also be sleeved where it passes through walls or floors to allow for thermal movement and leak detection.
What device should be installed on the fill point of a domestic oil storage tank?
Answer: An overfill prevention device (such as a tank gauge or electronic alarm)
An overfill prevention device is required to prevent the delivery driver from overfilling the tank. This can be an electronic gauge with alarm, a mechanical float gauge, or a whistle vent that changes tone as the tank fills.
What is the fire separation distance for a steel oil storage tank from a non-fire-rated building?
Answer: 1.0 metre minimum
Steel oil tanks require a minimum separation of 1.0 metre from a non-fire-rated building, compared to 1.8 metres for plastic tanks. Steel tanks are more fire-resistant, hence the reduced distance requirement.
How this page was made: written with AI tools and published by Nathan Beja, founder of Practice Test Geeks, who is responsible for its content. Exam facts are checked against the official sources listed below. Not reviewed by a subject-matter expert. Editorial policy
Sources & references
Exam facts on this page (fees, format, dates, passing scores) are checked against these official sources; the date is our last check. Editorial policy
- bpec.org.uk — Retake policy · verified Oct 2026
- oftec.org — Fees, renewal, eligibility, exam format, score validity, test delivery · verified Oct 2026