Oil Burner Types and Operation Flashcards

6 cards from real OFTEC practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 6 Oil Burner Types and Operation flashcards as text
  1. What does the term 'delayed ignition' mean in relation to oil burners?

    Answer: Oil is being delivered but fails to ignite immediately, causing a build-up

    Delayed ignition occurs when atomised oil enters the combustion chamber but does not ignite immediately. When it does ignite, the accumulated oil vapour causes a potentially dangerous 'puff back' or small explosion.

  2. What is the correct electrode gap setting typically specified for a domestic oil burner?

    Answer: 3-4mm between electrode tips

    The standard electrode gap for most domestic oil burners is approximately 3-4mm. Too narrow a gap may cause carbon bridging, while too wide a gap may prevent spark generation. Always refer to the manufacturer's specifications.

  3. Why must an oil burner fan run for a pre-purge period before ignition?

    Answer: To clear any residual oil vapour from the combustion chamber

    The pre-purge period allows the fan to push fresh air through the combustion chamber, clearing any residual oil vapour that could cause a dangerous puff back when ignition occurs. This is a critical safety feature.

  4. What is the purpose of the fire valve in an oil supply system?

    Answer: To automatically shut off the oil supply in the event of a fire

    A fire valve is a fusible link valve installed on the oil supply line near the appliance. In a fire, the fusible link melts (typically at 68°C), closing the valve and cutting off the fuel supply to prevent the fire being fed.

  5. What is a common cause of oil burner short cycling?

    Answer: An oversized burner or incorrect thermostat differential

    Short cycling occurs when the burner fires and shuts down too frequently. Common causes include an oversized burner for the heat load, too narrow a thermostat differential, or a faulty aquastat. This reduces efficiency and increases wear.

  6. What does a solenoid valve do in an oil burner system?

    Answer: Electrically opens and closes to control the flow of oil to the nozzle

    The solenoid valve is an electrically operated shut-off valve in the oil supply. It opens when the burner control box calls for heat and closes immediately when the burner stops, preventing oil from dripping into the combustion chamber.

How this page was made: written with AI tools and published by Nathan Beja, founder of Practice Test Geeks, who is responsible for its content. Exam facts are checked against the official sources listed below. Not reviewed by a subject-matter expert. Editorial policy

Sources & references

Exam facts on this page (fees, format, dates, passing scores) are checked against these official sources; the date is our last check. Editorial policy

  1. bpec.org.uk — Retake policy · verified Oct 2026
  2. oftec.org — Fees, renewal, eligibility, exam format, score validity, test delivery · verified Oct 2026