Combustion Efficiency Testing Flashcards
6 cards from real OFTEC practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 6 Combustion Efficiency Testing flashcards as text
What is the significance of the dew point temperature in condensing oil boilers?
Answer: It is the temperature at which water vapour in flue gases condenses, recovering latent heat
In condensing boilers, when flue gas temperature drops below the dew point (approximately 47°C for kerosene), water vapour condenses and releases latent heat. This recovered heat boosts efficiency above the theoretical 100% (gross) figure.
What is a CO/CO2 ratio and what does it indicate?
Answer: The proportion of CO to CO2 — a high ratio indicates dangerous incomplete combustion
The CO/CO2 ratio compares carbon monoxide (incomplete combustion) to carbon dioxide (complete combustion). A ratio above 0.004 indicates poor combustion that could be dangerous. It is a key safety indicator during testing.
What reading on a flue gas analyser would indicate a potentially dangerous appliance requiring immediate action?
Answer: CO reading above 200 ppm in the undiluted flue gas
CO readings above 200 ppm indicate severely incomplete combustion and an immediate danger. The appliance should be turned off, the customer warned not to use it, and a 'Do Not Use' label applied until repairs are completed.
Why must combustion readings be taken with all boiler covers and panels in place?
Answer: Removing covers changes the air supply and gives false readings that don't represent normal operation
Removing boiler covers changes the air flow to the burner, giving readings that do not represent how the boiler actually operates when the covers are fitted. Tests must replicate real operating conditions for accurate results.
What does a CO2 reading below 8% on a kerosene pressure jet burner typically indicate?
Answer: Excessive air is entering the combustion zone
A CO2 reading below 8% for kerosene indicates significantly too much excess air. This wastes heat up the flue, reduces efficiency, and may cause flame instability. The air band settings need adjusting to increase CO2 towards 10-12%.
What additional test should be performed if there is any suspicion of combustion gas spillage into the room?
Answer: A spillage test using smoke pellets or matches at the draught diverter
A spillage test uses smoke pellets or a match/taper at the draught diverter or flue break to check that combustion products are being drawn up the flue. If smoke is pushed into the room, there is a dangerous spillage condition.
How this page was made: written with AI tools and published by Nathan Beja, founder of Practice Test Geeks, who is responsible for its content. Exam facts are checked against the official sources listed below. Not reviewed by a subject-matter expert. Editorial policy
Sources & references
Exam facts on this page (fees, format, dates, passing scores) are checked against these official sources; the date is our last check. Editorial policy
- bpec.org.uk — Retake policy · verified Oct 2026
- oftec.org — Fees, renewal, eligibility, exam format, score validity, test delivery · verified Oct 2026