Combustion Efficiency Testing Flashcards

6 cards from real OFTEC practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 6 Combustion Efficiency Testing flashcards as text
  1. What is the purpose of a draught gauge (manometer) in oil burner testing?

    Answer: To measure the negative pressure (suction) in the flue system

    A draught gauge measures the negative pressure in the flue that draws combustion gases away from the burner. Correct draught (typically -0.02 to -0.05 mbar for oil) is essential for proper combustion and safe operation.

  2. What effect does a soot-covered heat exchanger have on combustion efficiency?

    Answer: It acts as insulation, reducing heat transfer to the water and increasing flue gas temperature

    Soot on the heat exchanger surfaces acts as an insulator, reducing heat transfer from combustion gases to the water. This causes higher flue gas temperatures and lower efficiency. Just 1mm of soot can reduce efficiency by 5%.

  3. When should a Bacharach smoke test be carried out during a service?

    Answer: After the burner has been running for at least 5 minutes at stable conditions

    The smoke test should be performed once the burner has reached stable operating conditions (at least 5 minutes running). This gives a representative reading. It is a standard part of every annual service, not just commissioning.

  4. What could cause a sudden increase in smoke number compared to previous service records?

    Answer: A worn nozzle, dirty air intake, or contaminated fuel supply

    Increased smoke numbers indicate deteriorating combustion. Common causes include a worn or partially blocked nozzle, restricted air supply (dirty filter or blocked air inlet), contaminated fuel, or incorrect pump pressure.

  5. What is the net flue gas temperature and why is it important?

    Answer: Flue gas temperature minus room temperature — it indicates how much heat is being lost

    Net flue gas temperature is calculated by subtracting the ambient room temperature from the measured flue gas temperature. This figure is used with the CO2 reading to calculate combustion efficiency and assess heat losses.

  6. How often should a flue gas analyser be calibrated?

    Answer: At least annually, with fresh air zeroing before each use

    Flue gas analysers must be professionally calibrated at least annually to maintain accuracy. Before each use, the instrument should be zero-calibrated in fresh air. Many instruments display a calibration due date.

How this page was made: written with AI tools and published by Nathan Beja, founder of Practice Test Geeks, who is responsible for its content. Exam facts are checked against the official sources listed below. Not reviewed by a subject-matter expert. Editorial policy

Sources & references

Exam facts on this page (fees, format, dates, passing scores) are checked against these official sources; the date is our last check. Editorial policy

  1. bpec.org.uk — Retake policy · verified Oct 2026
  2. oftec.org — Fees, renewal, eligibility, exam format, score validity, test delivery · verified Oct 2026
Combustion Efficiency Testing Flashcards — OFTEC Study Cards with Answers