← All OFTEC Flashcard Decks

Combustion Efficiency Testing Flashcards

6 cards from real OFTEC practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 6 Combustion Efficiency Testing flashcards as text
  1. What is the minimum acceptable combustion efficiency for a new oil-fired boiler at commissioning?

    Answer: 85%

    New oil-fired boilers should achieve a minimum combustion efficiency of 85% at commissioning. Modern condensing oil boilers typically achieve 90-95%. Lower readings indicate a problem requiring investigation.

  2. What does excess air in combustion mean for boiler efficiency?

    Answer: It reduces efficiency as heat is wasted heating unused air that goes up the flue

    Excess air beyond what is needed for combustion absorbs heat as it passes through the boiler and carries that heat up the flue. While some excess air is necessary for safe combustion, too much wastes energy.

  3. What is the correct position to take a flue gas sample from an oil-fired appliance?

    Answer: In the flue pipe, at the test point closest to the appliance outlet

    The flue gas sample should be taken from the test point in the flue pipe as close to the appliance flue outlet as practical. This gives the most accurate reading before the gases are diluted by any air ingress further up the flue.

  4. How long should an oil burner run before taking combustion readings?

    Answer: At least 10-15 minutes to reach stable operating conditions

    The burner should run for at least 10-15 minutes to reach stable operating conditions before taking readings. Cold-start readings are unreliable as the combustion chamber temperature affects the combustion process.

  5. What does a high oxygen (O2) reading in the flue gas indicate?

    Answer: Too much excess air is entering the combustion process

    High O2 readings (above 6-7% for kerosene) indicate excessive air entering the combustion zone. This lowers CO2, reduces efficiency, and may cause flame instability. The air band or damper needs adjusting.

  6. What is the relationship between CO2 and O2 readings in flue gas analysis?

    Answer: As CO2 increases, O2 decreases (they are inversely related)

    CO2 and O2 readings are inversely related. As more oxygen is consumed in combustion, CO2 production increases. Higher excess air dilutes the CO2 and increases O2. The ideal is to maximise CO2 while keeping O2 at a safe minimum.

How this page was made: written with AI tools and published by Nathan Beja, founder of Practice Test Geeks, who is responsible for its content. Exam facts are checked against the official sources listed below. Not reviewed by a subject-matter expert. Editorial policy

Sources & references

Exam facts on this page (fees, format, dates, passing scores) are checked against these official sources; the date is our last check. Editorial policy

  1. bpec.org.uk — Retake policy · verified Oct 2026
  2. oftec.org — Fees, renewal, eligibility, exam format, score validity, test delivery · verified Oct 2026