← All NEC Flashcard Decks

Load Calculations Flashcards

7 cards from real NEC practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 7 Load Calculations flashcards as text
  1. For a commercial occupancy, NEC 220.14(K) allows show window lighting to be calculated at what VA per linear foot as an alternative to actual load?

    Answer: 200 VA/ft

    NEC 220.14(K) permits show window lighting to be calculated at 200 VA per linear foot of show window as an alternative calculation method.

  2. When sizing a service for a school building with 50,000 sq ft, what VA per sq ft does NEC Table 220.12 specify for general lighting?

    Answer: 1.5 VA/sq ft

    NEC Table 220.12 assigns 1.5 VA per square foot as the unit load for schools.

  3. A 208V, 3-phase panel supplies a 30 kW balanced resistive load. What is the line current?

    Answer: 72.2A

    I = kW × 1000 ÷ (√3 × V) = 30,000 ÷ (1.732 × 208) ≈ 83.3A for a balanced 3-phase resistive load.

  4. Per NEC 220.83, what percentage of heating and cooling load is used in the optional calculation for existing dwelling service upgrades when both cannot operate simultaneously?

    Answer: 100% of larger, 0% of smaller

    NEC 220.83 uses only the larger of the heating or cooling load (noncoincident loads per 220.60) for existing dwelling optional calculations.

  5. What is the minimum calculated load for a 1,500 sq ft dwelling's general lighting before demand factors per NEC Table 220.12?

    Answer: 4,500 VA

    1,500 sq ft × 3 VA/sq ft = 4,500 VA per NEC Table 220.12 for dwelling occupancies before any demand factors.

  6. Under NEC 230.42, when a service entrance conductor carries a continuous load, it must be sized at a minimum of what percentage of the continuous load?

    Answer: 125%

    NEC 230.42(A) requires service entrance conductors to have an ampacity of at least 125% of the continuous load plus 100% of non-continuous loads.

  7. A warehouse with 80,000 sq ft requires a lighting load calculation. Using NEC Table 220.12, what unit load applies to warehouses?

    Answer: 0.25 VA/sq ft

    NEC Table 220.12 assigns 0.25 VA per square foot as the unit load for warehouses (storage).