When calculating the demand load for a commercial kitchen with six 5 kW ovens, what demand factor applies to the first 3 ovens per NEC Table 220.56?
Answer: 65%
NEC Table 220.56 applies a 65% demand factor to the first three commercial cooking appliances when four or more units are served from the same branch circuit or feeder.
A 200-ampere, 240-volt single-phase service supplies a dwelling. What is the net computed load in kVA that represents the full-load capacity of this service?
Answer: 48 kVA
Net computed load = 200 A × 240 V = 48,000 VA = 48 kVA for a single-phase service.
Under NEC 220.14(J), what is the unit load per outlet used for calculating branch-circuit loads for show-window lighting in a commercial occupancy?
Answer: 150 VA per linear foot
NEC 220.14(J) assigns 150 VA per linear foot of show-window space for branch-circuit load calculation purposes.
For optional calculation of a dwelling unit per NEC 220.82, which load is NOT included in the total connected load before applying demand factors?
Answer: Electric vehicle supply equipment
NEC 220.82 does not include EVSE in the optional calculation; EV loads are handled separately under Article 625 and NEC 220.57.
A 240-volt, 30-ampere dryer circuit serves a single household dryer. Per NEC 220.54, what is the minimum load to use when calculating the feeder demand for one dryer?
Answer: 5,000 VA
NEC 220.54 requires a minimum load of 5,000 VA (or the nameplate rating if higher) for each household dryer when calculating feeder demand.
When using the standard method to calculate a dwelling service, at what square footage threshold does the 3 VA per sq ft lighting load for the first portion end and require a different demand treatment under NEC Table 220.42?
Answer: The entire load uses demand factors; there is no square footage threshold
NEC Table 220.42 applies demand factors to the total general lighting load in VA (not square footage), with the first 3,000 VA at 100% and the remainder at 35%.
A three-phase, 208Y/120V panel serves 12 identical 1,500 VA single-phase receptacle loads balanced across phases. What is the total three-phase feeder load before demand factors?
Answer: 18,000 VA
Total load = 12 receptacles × 1,500 VA = 18,000 VA, which is then distributed across three phases but the total feeder VA is still 18,000 VA before demand factors.
How this page was made: written with AI tools and published by Nathan Beja, founder of Practice Test Geeks, who is responsible for its content. We have not yet matched this exam's facts to an official source, so confirm fees, dates and rules with the exam body. Not reviewed by a subject-matter expert. Editorial policy