  1. During a PV system inspection, you notice the output circuit conductors are routed through metal conduit with no separation from the grounding electrode conductor. What is the primary concern?

    Answer: Induced currents may cause heating in the metallic conduit

    Routing current-carrying conductors through metal conduit without including the return conductor can induce eddy currents in the conduit, causing heating.

  2. A technician inspects a string inverter and finds the DC input voltage is 15% above the inverter's maximum rated input voltage. What is the most likely cause?

    Answer: Ambient temperature is unusually low, increasing Voc

    Cold temperatures increase PV module open-circuit voltage (Voc), which can exceed inverter maximum DC input ratings if temperature correction was not applied during design.

  3. When inspecting a ground-mounted PV array, you observe rust staining on the mounting rails below the module clamps. What does this most likely indicate?

    Answer: Galvanic corrosion between dissimilar metals at the clamp interface

    Rust staining at clamp interfaces typically indicates galvanic corrosion caused by contact between dissimilar metals such as aluminum rails and steel fasteners without proper isolation.

  4. An inspector finds that the AC disconnect is labeled with a voltage rating of 240V but is installed on a 208V three-phase system. What is the appropriate finding?

    Answer: This is acceptable since 240V exceeds 208V

    Electrical equipment may be used at voltages at or below its voltage rating; a 240V-rated disconnect is acceptable on a 208V system.

  5. During a commissioning inspection, you identify that the PV source circuit fuses are rated at 20A but the module's maximum series fuse rating (Isc × 1.25 × 1.25) calculates to 15A. What action is required?

    Answer: Replace the fuses with properly sized 15A fuses

    Overcurrent protection devices must not exceed the module's maximum series fuse rating to protect module wiring and cells from reverse current damage.

  6. A rooftop PV system inspection reveals that module frames are bonded using module-to-module bonding washers but the first and last modules in each row are not connected to the equipment grounding conductor. What code requirement is violated?

    Answer: NEC 690.43 requiring all exposed metal parts to be grounded

    NEC 690.43 requires all exposed non-current-carrying metal parts of PV module frames and equipment to be connected to an equipment grounding conductor.

  7. When inspecting combiner box connections, a technician measures a 2V voltage drop across a string fuse under load. The fuse is rated for the correct ampacity. What does this reading indicate?

    Answer: A loose or corroded fuse connection creating excessive resistance

    A significant voltage drop across a properly rated fuse indicates high resistance at the fuse or its connection, typically from corrosion or a loose connection that requires remediation.