What is the standard unit load per square foot used for general lighting in office buildings per the NEC?
Answer: 3.5 VA
NEC Table 220.12 specifies a unit load of 3.5 VA per square foot for general lighting in office buildings.
How many current-carrying conductors can occupy a single conduit before derating factors must be applied per the NEC?
Answer: 3
Ampacity adjustment factors from NEC Table 310.15(C)(1) apply when more than 3 current-carrying conductors are in a single raceway.
What is the power factor of a purely resistive AC circuit?
Answer: 1.0
A purely resistive AC circuit has a power factor of 1.0 because voltage and current are perfectly in phase.
Per the NEC, what is the minimum height above a rooftop for service drop conductors with a roof slope greater than 4 inches in 12 inches?
Answer: 3 feet
NEC 230.24(A) permits a reduction to 3 feet of clearance above a roof with a slope greater than 4 inches in 12 inches.
What is the total impedance of a series RLC circuit with R = 30 ohms, XL = 50 ohms, and XC = 10 ohms?
Answer: 50 ohms
Total impedance is calculated as Z = sqrt(R² + (XL - XC)²) = sqrt(900 + 1600) = 50 ohms.
What is the maximum number of 90-degree bends permitted between pull points in a conduit run per the NEC?
Answer: 4
NEC 358.26 limits conduit runs to a maximum of 360 degrees of total bends (equivalent to four 90-degree bends) between pull points.