Licensed Electrical Contractor Cheat Sheet 2026
The 30 highest-yield Licensed Electrical Contractor facts, distilled from real exam questions. Print it, save it as a PDF, or study it here โ free, no sign-up.
100 questions
240 min time limit
75% to pass
- According to NEC 250.122, how is the minimum size of an equipment grounding conductor determined for a branch circuit? โ By the rating of the overcurrent device protecting the circuit
- According to NEC Article 250, the main purpose of equipment grounding conductors (EGC) is to: โ Provide a low-impedance fault current path to facilitate overcurrent device operation
- Per NEC 230.71(A), what is the maximum number of service disconnecting means permitted for a single service? โ 6 disconnects
- When should you replace a circuit breaker? โ When they fail to reset or show damage.
- When must a licensed electrical contractor provide Safety Data Sheets (SDS) to employees under the OSHA Hazard Communication Standard? โ SDS must be readily accessible to employees during their work shift
- Which of the following best defines a 'Readily Accessible' location according to NEC Article 100? โ Capable of being reached quickly without climbing over or removing obstacles.
- What is the primary purpose of a mechanics lien in the electrical contracting business? โ To secure payment for labor and materials provided on a construction project
- Which NFPA standard is commonly known as the National Electrical Safety Code (NESC) and covers utility installations? โ NFPA 70 does not cover utilities; the NESC is IEEE C2
- Which type of electrical current periodically reverses direction? โ Alternating current (AC)
- Two 40-microfarad capacitors are connected in series. What is the total capacitance of the combination? โ 20 ยตF
- What is the maximum penalty per violation that OSHA can impose on an electrical contractor for a willful safety violation as of current federal guidelines? โ $161,323
- What should be used to protect circuits from overloads? โ Circuit breakers or fuses.
- What is the total impedance of a series RLC circuit with R = 30 ohms, XL = 50 ohms, and XC = 10 ohms? โ 50 ohms
- For a parallel conductor installation using two sets of 500 kcmil conductors per phase, what is the NEC requirement for conductor arrangement? โ Each phase must have the same length, type, and termination method
- Which type of fire extinguisher is appropriate for use on an energized electrical fire? โ Class C
- The NEC requires GFCI protection for 125V, 15- and 20-amp receptacles in: โ Bathrooms, kitchens within 6 feet of sink, and outdoors
- What does the term 'scope of work' define in an electrical contracting agreement? โ The specific tasks, deliverables, and boundaries of the contracted work
- A young worker (under 18) hired by an electrical contractor may be restricted from certain tasks under which federal law? โ The Fair Labor Standards Act (FLSA)
- Under NEC 210.52, GFCI protection is required for all receptacles within how many feet of the outside edge of a bathroom sink? โ 6 feet
- What is the minimum rating required for any branch circuit that supplies two or more outlets or receptacles per NEC 210.3? โ 15 amperes
- What is the purpose of a transformer in an electrical circuit? โ To change the voltage level in an AC circuit.
- When troubleshooting a motor that hums but does not start, which component should be checked first? โ Start capacitor
- Under NEC 110.26, the minimum required working clearance in front of electrical equipment operating at 120V to ground in a Condition 1 environment is: โ 3 feet
- What does NEC 110.14 primarily address? โ Electrical connections and terminals
- What is the primary purpose of equipment bonding jumpers in an electrical system? โ To ensure electrical continuity and conductivity between metal parts
- What is the function of a grounding electrode in an electrical system? โ To safely discharge fault current into the earth.
- Which of the following wiring methods is NOT permitted in a commercial garage as defined by NEC Article 511? โ Type NM cable
- How often should electrical maintenance be performed on commercial systems? โ At least once a year.
- According to NEC 110.26, the minimum depth of working space required in front of electrical equipment rated 600V or less (Condition 1) is: โ 3 feet
- A 14 AWG copper conductor on a 15-ampere branch circuit can safely supply a maximum continuous load of how many amperes? โ 12 amperes
Turn these facts into recall:
What Practice Test Geeks adds beyond an AI chat for Licensed Electrical Contractor
An AI chatbot can quiz you, but it can't reproduce the exam conditions or keep your record. Here you get:
- A timed, full-length Licensed Electrical Contractor mock exam โ 100 questions in 240 minutes with a 75% pass mark, modeled on the official exam's question count and time limit, followed by a score report broken down by exam domain.
- A fixed Licensed Electrical Contractor question bank: the same test every attempt, so your score is comparable from one try to the next instead of changing with every regenerated quiz.
- Progress saved on your device: completed tests, scores and missed questions stay in My Progress, so you can retake only what you got wrong.
- Licensed Electrical Contractor flashcards built from the same question bank.
- Free Licensed Electrical Contractor practice tests with the correct answer shown after each question.
Was this helpful?
Written and edited by Nathan Beja, founder of Practice Test Geeks, with AI assistance. Exam facts are checked against the official sources linked below. Editorial policy
Sources & references
Exam facts on this page (fees, format, dates, passing scores) are checked against these official sources; the date is our last check. Editorial policy
- cslb.ca.gov โ Eligibility, fees, renewal ยท verified Nov 2026
- www2.myfloridalicense.com โ Exam format, passing score, retake policy, score release, time limit, test delivery, test dates ยท verified Nov 2026
- ncbeec.org โ Test delivery, fees, exam format, passing score, retake policy, score release, test dates, time limit ยท verified Nov 2026