← All ISA CAP Flashcard Decks

Control Systems & Instrumentation Flashcards

7 cards from real ISA CAP practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 7 Control Systems & Instrumentation flashcards as text
  1. According to IEC 61511, what is the difference between a Safety Instrumented System (SIS) and a Basic Process Control System (BPCS)?

    Answer: A SIS is designed to bring the process to a safe state upon demand, independent of the BPCS

    IEC 61511 requires the SIS to be independent of the BPCS so that a BPCS failure does not compromise the safety function.

  2. A vortex flow meter operates on which physical principle?

    Answer: The frequency of vortices shed by a bluff body is proportional to fluid velocity

    Vortex meters count the frequency of alternating vortices shed from a bluff body (Von Kármán effect), which is directly proportional to volumetric flow velocity.

  3. In ISA-5.1 notation, what does the letter 'Y' as a succeeding letter in a tag identifier indicate?

    Answer: A relay or computing function (e.g., computation, conversion, switching)

    Per ISA-5.1, 'Y' as a succeeding identifier letter denotes a relay, computing, or converting function such as a signal selector or arithmetic device.

  4. What is 'reset windup protection' designed to prevent in a PID controller?

    Answer: Accumulation of integral action while the output is at its limit, causing overshoot on recovery

    Reset windup protection (anti-windup) limits integral accumulation when the output saturates, preventing large overshoot when the output constraint is lifted.

  5. Which of the following best describes 'feedforward control' in a process control application?

    Answer: Predictive control action based on measured disturbances before they affect the process variable

    Feedforward control measures known disturbances and takes corrective action before the disturbance affects the controlled variable, complementing feedback control.

  6. What is the typical output signal range of a pneumatic controller in industrial process control?

    Answer: 3-15 psi

    The standard pneumatic signal range for industrial controllers and valve actuators is 3-15 psi (approximately 20-100 kPa).

  7. During loop tuning, if increasing the proportional gain causes sustained oscillations at a constant amplitude, the loop is operating at:

    Answer: The ultimate gain condition where the phase margin equals zero

    Sustained constant-amplitude oscillations indicate zero phase margin (ultimate gain condition), where the open-loop phase shift equals -180° at the gain crossover frequency.

How this page was made: written with AI tools and published by Nathan Beja, founder of Practice Test Geeks, who is responsible for its content. Exam facts are checked against the official sources listed below. Not reviewed by a subject-matter expert. Editorial policy

Sources & references

Exam facts on this page (fees, format, dates, passing scores) are checked against these official sources; the date is our last check. Editorial policy

  1. isa.org — Fees, registration deadline, test dates, score validity, retake fee, retake policy, score release, time limit · verified Oct 2026