Testing and Quality Assurance Flashcards
7 cards from real ICC practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 7 Testing and Quality Assurance flashcards as text
Under the IBC, what is required when a building owner disputes the results of a special inspection?
Answer: The owner may appeal to the board of appeals or request additional testing as determined by the building official
Disputes over inspection findings may be resolved through the board of appeals process or additional testing authorized by the building official.
Per the IMC, what test must be performed on refrigerant-containing systems after installation?
Answer: Leak test using approved detection methods at operating or test pressure
The IMC requires that refrigerant systems be leak tested after installation using approved leak detection methods to ensure no refrigerant is escaping.
Under the IPC, what is the required test pressure for potable water supply piping systems?
Answer: 100 psi for 15 minutes or operating pressure plus 50 psi for 15 minutes
IPC requires water supply systems to be tested at 100 psi or 50 psi above operating pressure, whichever is greater, for 15 minutes without leakage.
Which ASTM standard is referenced in the IBC for testing the fire-resistance rating of through-penetration firestop systems?
Answer: ASTM E814
ASTM E814 (UL 1479) is the standard test method for fire tests of through-penetration firestops, required when pipes or conduits pass through fire-rated assemblies.
Under IBC Chapter 17, what documentation must the approved agency retain after completing special inspections?
Answer: Inspection reports must be retained for a minimum period and made available to the building official upon request
IBC requires approved agencies to retain inspection records and make them available to the building official; these records support the final certification.
What is the ICC-referenced standard for testing steel moment frame connections in seismic applications?
Answer: AISC 341 — Seismic Provisions for Structural Steel Buildings
AISC 341 provides the seismic provisions for structural steel, including testing and qualification requirements for moment frame connections in seismic design categories.
Under the IBC, when is a 'peer review' of special inspection programs required?
Answer: When required by the building official for unusual or complex structures
The building official may require independent peer review of the special inspection program for structures with unusual complexity or risk.
How this page was made: written with AI tools and published by Nathan Beja, founder of Practice Test Geeks, who is responsible for its content. Exam facts are checked against the official sources listed below. Not reviewed by a subject-matter expert. Editorial policy
Sources & references
Exam facts on this page (fees, format, dates, passing scores) are checked against these official sources; the date is our last check. Editorial policy
- iccsafe.org — Retake policy, score release, renewal, score validity, test delivery, passing score, exam format, time limit · verified Oct 2026
- shop.iccsafe.org — Fees · verified Oct 2026