Mixed Deck — All HVAC Topics Flashcards
100 cards from real HVAC practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 20 Mixed Deck — All HVAC Topics flashcards as text
A recovery cylinder is color-coded gray with a yellow top. What does this indicate?
Answer: The cylinder is a recovery cylinder for used (recovered) refrigerant
Under AHRI Guideline N, a gray body with a yellow top marks a recovery cylinder: it holds used refrigerant that has been recovered from a system and has not been reclaimed. The color does not identify a specific refrigerant, and it does not mean the contents are mixed or unknown. Always check the label for the actual refrigerant inside.
What IAQ hazard does a malfunctioning heat exchanger in a forced-air furnace pose?
Answer: Carbon monoxide (CO) poisoning from combustion gases leaking into the supply air stream
A cracked or corroded heat exchanger allows combustion gases—including deadly carbon monoxide—to mix with the circulated air supply, posing serious carbon monoxide poisoning risk.
What role does collaboration play in energy efficiency for HVAC professionals?
Answer: It enhances outcomes through diverse perspectives and shared expertise
Collaboration leverages diverse perspectives and combined expertise to achieve better outcomes than any individual could alone.
In a demand-controlled ventilation (DCV) system, CO2 sensors are used to:
Answer: Modulate outdoor air dampers based on occupancy levels
DCV uses CO2 as a proxy for occupancy; as CO2 rises above setpoint (typically 1100 ppm), the controller opens outdoor air dampers to dilute contaminants and provide fresh air.
What type of mastic sealant is recommended for sealing HVAC duct joints in unconditioned spaces?
Answer: UL 181-listed water-based duct mastic applied with mesh tape
UL 181-listed duct mastic reinforced with fiberglass mesh tape provides a durable, airtight seal that remains flexible across temperature cycles in unconditioned spaces.
What is a 'Variable Air Volume' (VAV) system and how does it differ from a 'Constant Volume' (CAV) system?
Answer: VAV varies supply air volume to each zone while maintaining constant supply temperature; CAV delivers constant air volume at varying temperatures
A VAV system delivers conditioned air at constant supply temperature but modulates the volume delivered to each zone using VAV terminal boxes, matching supply to actual demand.
What problems arise from excessively high water velocity in hydronic piping?
Answer: High velocity causes erosion-corrosion, noise, and air entrainment
Excessively high water velocity causes erosion-corrosion at fittings and elbows, generates flow noise, and can cause air bubbles to be entrained.
What is the maximum fill level (by weight) allowed when filling a refrigerant recovery cylinder?
Answer: 80% of the cylinder's rated capacity
Recovery cylinders must not be filled beyond 80% of their rated capacity to allow for liquid refrigerant expansion with temperature changes.
What is the purpose of a heat exchanger when connecting a hydronic loop to a pool or snowmelt slab?
Answer: To provide thermal and hydraulic isolation between loops with different water quality, chemicals, or pressure ratings
A plate heat exchanger separates the primary heating loop from secondary loops that may contain different chemicals or operate at different pressures, while efficiently transferring heat.
Which approach is recommended for troubleshooting system design issues?
Answer: Use systematic isolation and testing methods
Systematic isolation and testing methodically narrows down the root cause, making troubleshooting efficient and accurate.
Which professional attribute is most valued in ductwork within the HVAC field?
Answer: Accountability and commitment to standards
Accountability and commitment to professional standards build trust and ensure consistent, high-quality practice.
A technician discovers that a customer's existing refrigerant lines contain R-22. Which statement about handling this refrigerant is CORRECT?
Answer: R-22 must be recovered using EPA Section 608-certified equipment
EPA Section 608 prohibits venting R-22 and requires recovery using certified equipment; R-22 production ended in 2020 but existing supplies must still be properly handled.
What is the 'breathing zone' as defined by ASHRAE 62.1?
Answer: The region within an occupied space between 3 and 72 inches above the floor and more than 2 feet from walls—where occupants breathe
ASHRAE 62.1 defines the breathing zone as 3-72 inches above floor level, more than 2 feet from walls or fixed HVAC equipment—this zone must meet ventilation rate requirements.
What is 'transcritical CO2' (R-744) heat pump technology and where is it most applicable?
Answer: A refrigeration cycle where CO2 operates above its critical point on the high-pressure side; particularly advantageous for heat pump water heating and cold climate heating applications
Transcritical CO2 systems operate the high-pressure side above CO2's critical point (88°F/1071 psi), which makes them highly effective for heat pump water heating (achieving 150°F+ outlet temperatures) and heating in cold climates.
What problem does a 'magnetic dirt separator' solve?
Answer: Captures ferrous particles from corrosion before they damage pump bearings and heat exchangers
Magnetic dirt separators use powerful magnets to capture iron oxide particles (magnetite) created by corrosion inside steel and cast iron components, protecting pumps, valves, and heat exchangers.
What safety device shuts off a gas furnace if the heat exchanger area overheats?
Answer: High-limit switch
The high-limit switch senses supply air or heat exchanger temperature and shuts down the burner if the temperature exceeds a safe threshold.
A condensing furnace produces water drainage as a byproduct. What causes this condensation?
Answer: Combustion gases cooling below their dew point in the secondary heat exchanger
Condensing furnaces extract so much heat that flue gases cool below their dew point (~130°F), causing water vapor in the exhaust to condense.
What is 'Cold Climate' or 'H1C' specification for air-source heat pumps?
Answer: NEEP's specification requiring heat pumps maintain at least 70% of rated capacity at 5°F outdoor and provide capacity down to -13°F or lower
The Northeast Energy Efficiency Partnerships (NEEP) Cold Climate Air Source Heat Pump (ccASHP) specification requires maintaining ≥70% of rated capacity at 5°F outdoor and operation down to -13°F.
What does an enthalpy controller measure to determine if economizer free-cooling is beneficial?
Answer: Both outdoor air temperature and humidity to calculate total heat content
An enthalpy controller measures both outdoor dry-bulb temperature and wet-bulb temperature (or relative humidity) to calculate total heat content (enthalpy) and enable economizer mode only when outdoor air is truly beneficial.
What refrigerant classification system is used by ASHRAE to categorize refrigerant safety?
Answer: Class A/B for toxicity and 1/2/3 for flammability
ASHRAE Standard 34 uses a two-part safety classification: A or B for toxicity (A = lower toxicity, B = higher toxicity) and 1, 2L, 2, or 3 for flammability (1 = no flame propagation, 3 = high flammability).