Electrical Controls Flashcards
7 cards from real HVAC practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 7 Electrical Controls flashcards as text
A motor starting capacitor (electrolytic) differs from a run capacitor (film/oil) in that it is rated for:
Answer: Intermittent duty only — seconds per start
Start capacitors are electrolytic and designed for intermittent use only; leaving them in circuit continuously will cause them to overheat and fail.
When testing a run capacitor with a digital capacitance meter, an acceptable reading is typically within what percentage of the nameplate rating?
Answer: ±6%
Industry standard allows run capacitors to be within ±6% of their rated capacitance; readings outside this range indicate a failing capacitor.
What is the purpose of a lockout-relay (anti-short-cycle timer) in a refrigeration control circuit?
Answer: Prevent the compressor from restarting too quickly after shutdown
An anti-short-cycle timer delays compressor restart (usually 3–5 minutes) to allow pressure equalization and prevent motor overload from rapid cycling.
In a heat pump system, the 'O' or 'B' terminal on the thermostat controls the:
Answer: Reversing valve solenoid
The O (or B) terminal energizes the four-way reversing valve solenoid, switching the refrigerant flow direction between heating and cooling modes.
A technician measures 0 VAC across a normally-open contactor contact set while the coil is energized. This indicates:
Answer: The contacts are closed and conducting normally
When contacts close and conduct properly, the voltage across them drops to near zero because there is no resistance across a good closed contact.
An economizer control on a commercial HVAC unit uses which primary signal to determine if outside air can provide free cooling?
Answer: Outside air enthalpy or dry-bulb temperature compared to return air
Economizer controllers compare outside air enthalpy (or temperature) to return air conditions; when outside air is cooler/drier, the damper opens for free cooling.
Which NEMA enclosure rating is required for electrical controls installed outdoors and exposed to rain?
Answer: NEMA 3R
NEMA 3R enclosures are rainproof and suitable for outdoor use, protecting controls from falling rain, sleet, and external ice formation.