← All G60 Flashcard Decks

Personal Protective Equipment and Work Area Setup Flashcards

6 cards from real G60 practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 6 Personal Protective Equipment and Work Area Setup flashcards as text
  1. What is the minimum safe distance cylinders should be kept from the actual torch flame during operations?

    Answer: At least 10 feet (approximately 3 meters)

    Gas cylinders must be kept at least 10 feet from open flames or any heat source to prevent heat buildup that could dangerously increase internal cylinder pressure.

  2. How must gas cylinders be secured during storage and use?

    Answer: Chained or strapped upright to a wall, post, or cylinder cart

    Cylinders must always be chained or strapped in an upright position to prevent them from falling, which can damage the valve and cause an uncontrolled release of pressurized gas.

  3. What action must be taken before moving a gas cylinder from one location to another?

    Answer: Close the valve, remove the regulator, and replace the valve protection cap

    Before moving a cylinder, close the valve completely, remove the regulator to protect it from damage, and replace the protective valve cap to guard the valve during transport.

  4. Why must oxygen and fuel gas cylinders be stored separately?

    Answer: To prevent a leak from one type reaching the other and creating a flammable mixture

    Oxygen and fuel gas cylinders must be separated by at least 20 feet or a 5-foot non-combustible firewall because a fuel gas leak could create a combustible atmosphere ignited by the oxygen.

  5. What type of signage is required at the entrance to an area where flammable gas torch work is being performed?

    Answer: Warning signs prohibiting smoking and open flames, and identifying the hazard

    The work area entrance must be marked with warning signs prohibiting smoking and identifying the flammable gas hazard to alert others before they enter.

  6. What must be present in the immediate work area before torch operations begin?

    Answer: An appropriate fire extinguisher rated for the potential hazards present

    An appropriate fire extinguisher — typically a dry chemical or CO2 type rated for the combustible materials present — must be immediately accessible in the torch work area.