FREE Registered Communications Distribution Designer (RCDD): Case Studies and Concepts Questions and Answers

0%

When planning the layout of a data center housing high-density servers, which type of system for managing airflow should be given top priority to ensure effective cooling?

Correct! Wrong!

The correct answer is Hot/cold aisle containment. In data centers with high-density servers, hot/cold aisle containment is crucial for efficient cooling. This strategy involves segregating hot and cold airflows, preventing them from mixing and ensuring that the servers receive cooler air and exhaust warmer air, leading to improved cooling efficiency and overall data center performance.

In terms of perimeter raceway systems, what is their primary intended purpose?

Correct! Wrong!

The correct answer is Small floor areas where the majority of telecommunication services will be along the walls. Perimeter raceway systems are particularly suitable for environments where there is limited space and where most of the telecommunication services are concentrated along the walls. This setup allows for efficient and organized cable routing, especially in spaces where floor area might be constrained but wall spaces can accommodate the necessary cabling infrastructure.

In the scenario where you need to connect a cable between two equipment locations with distinct grounds, resulting in a potential difference of 2.1 V rms, which among the provided cable options should be avoided for this purpose?

Correct! Wrong!

The correct answer is STP (Shielded Twisted Pair). When connecting a cable between two equipment locations with separate grounds and a potential difference of 2.1 V rms, Shielded Twisted Pair (STP) cables should be avoided. STP cables are designed to offer better protection against electromagnetic interference (EMI) and potential differences, and using them in this scenario may exacerbate the problem of having distinct grounds, potentially leading to ground loop issues or interference. Therefore, a different cable type should be considered to mitigate these potential issues.

While installing Category 6 unshielded twisted-pair (UTP) cables within a cable tray along a hallway adjacent to the elevator mechanical room, what precautionary measure should be implemented to mitigate the potential impact of electromagnetic interference (EMI)?

Correct! Wrong!

The correct answer is Provide a minimum separation of 1194 mm (47 in). To mitigate the effects of electromagnetic interference (EMI) when placing Category 6 unshielded twisted-pair (UTP) cables in a cable tray near an elevator mechanical room, it's advisable to maintain a minimum separation of 1194 mm (47 in) between the cable tray and the mechanical room. This separation helps prevent unwanted electromagnetic interference from adversely affecting the performance of the cables, ensuring optimal signal transmission and reception.

Among the options provided, which one does not represent a benefit associated with access floor systems?

Correct! Wrong!

The correct answer is They have a low initial cost. While access floor systems offer advantages like high capacity, easy access to cabling, and the ability to make changes with minimal disruption, having a low initial cost is not typically a characteristic of these systems. Access floor systems often involve additional costs due to their specialized design and installation requirements, which can lead to increased upfront expenses compared to traditional flooring options.

In your design of a horizontal pathway system involving 100 mm (4 in) conduit and pull boxes, considering architectural limitations for a single conduit layer (non-stacked), and comprising a main pathway system with five 100 mm (4 in) conduits, what is the smallest required width for the pull box?

Correct! Wrong!

The correct answer is 1220 mm (48 in). Given the constraints of a single conduit layer and the presence of five 100 mm (4 in) conduits in the main horizontal pathway system, the minimum width for the pull box is 1220 mm (48 in). This width ensures adequate space for cable pulling, routing, and potential changes while accommodating the specified conduit layout.

Among the choices provided, which category of cable tray is most accurately characterized by having a bottom with ventilation openings and side rails?

Correct! Wrong!

The correct answer is Ventilated trough. A cable tray with a ventilated bottom and side rails is accurately represented by the term "ventilated trough." This type of cable tray design allows for proper air circulation around the cables while providing structural support through the side rails. The ventilation feature is especially beneficial for dissipating heat generated by the cables and ensuring efficient cable management within the tray.

Premium Tests $49/mo
FREE December-2024